Honeywell SV2 Series User Manual page 39

Safety shut-off valves
Table of Contents

Advertisement

Table 7. Factory Wiring Information.
Description
Purpose
SOLENOID 1
Connection from Solenoid 1 to main electronics. Enables powering of solenoid.
SOLENOID 2
Connection from Solenoid 2 to main electronics. Enables powering of solenoid.
PROOF OF CLOSURE
POC 1
Connection from Solenoid 1 POC to main electronics. Tied to the valve interface
Open and Closed LEDs. Refer to
POC 2
Connection from Solenoid 2 POC to main electronics. Tied to the valve interface
Open and Closed LEDs. Refer to
FUEL/AIR
Module that measures gas, air and gas/air mix inputs from fuel/air system to
control the fuel/air premix valves. Works with stepper MOTOR.
MOTOR
Stepper motor performs valve modulation in response to changing conditions from
the fuel/air module and burner system
Table 8. Field Wiring and Terminal Designation
Description
MAINS SUPPLY
1
GROUND
(PROTECTIVE EARTH PE)
CONTROL WIRING
2
RS-485 MODBUS
2
MODBUS BIAS RESISTORS
PRESSURE
SV2 Series Safety Shut-off Valves
V2F, V2V
Fig. 14
Fig. 14
.
4
Terminal
Purpose
L1
Valve incoming voltage supply L1 connection
N
Valve incoming voltage supply neutral connection
MAINS
Valve external ground connection
CHASSIS
Valve chassis ground, connected to valve body grounding terminal
ILK OUT
Interlock wiring run through all valve models for solenoid power saving
feature. Dry contact output / input also used for flame safeguard control
ILK string with Pressure Module for low gas pressure and high gas
ILK IN
pressure functions.
Line voltage output for Valve Proving System switch, using the Pressure
VPS SW
Module, for external VPS conducted by a separate device
POC
Line voltage output for Proof of Closure switch
MV2
3
Main valve 2 and 1 incoming voltage from burner control. May be
jumpered if external VPS is NOT performed or if valve is an internal VPS
model (models with Intelligent Features of 8 or 9)
MV1
3
+
Modbus Data + connection
-
Modbus Data - connection
C
Modbus common connection
BIAS
Bias resistor for differential resistance
TERM.
Termination resistor
BIAS
Bias resistor for differential resistance
Field connection for Pressure Module, which can be used for Low gas
-
pressure, High gas pressure, VPS (external and internal), Leak detection
or pressure monitoring
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
and
Fig.
21.
and
Fig.
21.
Rating
24, 100-240VAC,15W
24, 100-240VAC, 8A
24, 100-240VAC, 0.1A
24, 100-240VAC, 0.1A
1 inch / DN25 Valves:
1.5/2.0 inch / DN40-50 Valves:
Per coil pull-in (2 sec) at 20°C/68°F
For HMI or PC Tools or building
automation system connection
Refer to section F.entitled Valve
Modbus Bias Setup
39
Applicable Model(s)
(optional)
Applicable
6
Model(s)
All
All
-
All
All models with Intelligent
Features of 6 or 7
All valves with POC
24VAC, 1.6A/35W
120VAC, 0.5A/55W
240VAC, 0.3A/55W
All
120VAC, 1.0A/110W
240VAC, 0.6A/110W
All models with Intelligent
Features of 6, 7, 8 or 9
All models with Intelligent
Features of 6, 7, 8 or 9
All models with Intelligent
-
Features of 6, 7, 8 or 9
All
All
V2V
V2V
5