SV2 Series Safety Shut-off Valves
VALVE FAULT CODES
There are several possible fault conditions, some of which are dependent on the valve configuration ordered and installed
accessories. The HMI and PC Tools provide detailed fault code descriptions and remediation steps for the operator to follow to
rectify any fault condition. The information in this section details all of the possible fault codes and their remediation steps.
NOTE: Upon valve reset after a fault, the software will not allow the valve seats to be re-powered by the burner control for 7
seconds to accommodate various flame failure response timings.
Table 26. SV2 Series Fault Conditions.
Fault
Fault
Category
Description
Data Error EEPROM
corrupt
EEPROM
lockout code
mis-match
Valve body
parameter
missing
Fuel/Air
Air flow sensor
(S1) out of
range
Detailed Description
Main electronics EEPROM is
corrupt.
Main electronics EEPROM
lockout code storage value
incorrect.
Valve body parameters
not defined in electronics
memory. This may occur
when the valve main
electronics have been
replaced in the field.
The airflow sensor signal
is/was outside the sensor
measuring range (-8000 to
8000).
Remediation Steps
1.) Reset valve and burner management
system then cycle power.
2.) If fault persists replace main
electronics.
3.) Recommission all valve parameters.
1.) Reset valve and burner management
system then cycle power.
2.) If fault persists replace main
electronics.
Set valve body parameters by accessing
the valve guided setup screens.
1.) Reset valve and burner management
system.
2.) If fault persists, replace Fuel/Air
Module.
3.) Reset valve and burner management
system.
4.) Accept new Fuel/Air Ratio Module on
the FARMOD tab in the Setup & Tests
menu of user interface.
5.) Recommission partially or fully as
desired.
176
Comments Fault
#
23
24
48
18
32-00029—02