Honeywell SV2 Series User Manual page 221

Safety shut-off valves
Table of Contents

Advertisement

Address
Type
Dec
Hex
57
39
58
3A
59
3B
60
3C
61
3D
62
3E
270
10E
271
10F
VPS
272
110
273
111
274
112
275
113
276
114
277
115
682
2AA
683
2AB
684
2AC
685
2AD
686
2AE
687
2AF
689
2B1
690
2B2
691
2B3
692
2B4
693
2B5
694
2B6
Note:
Input registers 139 – 213 contain the fault history. The last 15 fault records are stored. Each record consists of 5 consecutive input registers; 1 input register holds the fault code, 2 input registers hold
the time stamp and 2 input registers hold the valve cycle count recorded at the moment of fault occurrence. The time stamp is recorded with resolution 0.25 hr.
The 4 time stamp / cycle count input registers for each fault contain a 32-bit value stored in mode 3-2-1-0. The input register with lower number contains the upper bytes of the 32-bit number (bytes 3 and
2) and the input register with higher number contains the lower bytes of the 32-bit number (bytes 1 and 0).
SV2 Series Safety Shut-off Valves
V2F, V2V
Valve
Intelligence
Description
Model
Levels
VPS Valve 2 valve status
Input pressure measured during VPS
Output pressure measured during VPS
Valve 1 maximum leakage detected during last VPS
sequence.
Shown in user selected flow units.
Valve 2 maximum leakage detected during last VPS
sequence.
Shown in user selected flow units.
VPS minimum test time requirement for burner
control
Valve 1 accumulated hours recorded during
last VPS sequence
All
Standard
Valve 1 accumulated cycles recorded during
last VPS sequence
Valve 2 accumulated hours recorded during
last VPS sequence
Valve 2 accumulated cycles recorded during
last VPS sequence
VPS recorded leakage rate for MV1
Number of averaged VPS measurements for MV1
Recorded valve cycles during MV1 VPS test
VPS test execution time for MV1
VPS recorded leakage rate for MV2
Number of averaged VPS measurements for MV2
Recorded valve cycles during MV2 VPS test
VPS test execution time for MV2
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Data
Content
Type
0 =Test has not been performed yet
1 =Test was started
3 =Leakage has been calculated
4 =Test is finished
Enum
0x83=Leakage is over leakage limit
0x84=Wrong pressure level detected during initialization
of VPS test
0xFF=VPS function disabled
U16
Pressure.
See Holding Register 74 for user selected units.
U16
Volumetric flow.
S16
See Holding Register 75 for selected units.
Volumetric flow.
S16
See Holding Register 75 for selected units.
S16
Time in seconds
U16
Upper word
U16
Lower word
U16
Upper word
U16
Lower word
U16
Upper word
U16
Lower word
U16
Upper word
U16
Lower word
S16
Expressed in units selected by user during setup
U16
Dimensionless number
U16
Upper word
U16
Lower word
U16
Upper word, resolution 0.25 hours
U16
Lower word, resolution 0.25 hours
S16
Expressed in units selected by user during setup
U16
Dimensionless number
U16
Upper word
U16
Lower word
U16
Upper word, resolution 0.25 hours
U16
Lower word, resolution 0.25 hours
221