SV2 Series Safety Shut-off Valves
NOTE: If the valve is powered during the safety verification procedure, it will not be un-powered, unless a fault occurs.
Depending on whether the attached valve is un-configured or configured and whether the configuration has or does not have
passwords, there are slightly different cloning procedures to be followed as detailed next.
Unconfigured Valve Procedure
1.
With the valve connected to the user interface (HMI Tool or PC Tool), navigate to the Home page. The attached
unconfigured valve(s) are identified via the text 'Unconfigured' at the bottom of the valve tile(s). Refer to
Fig. 99: Unconfigured valve tile on user interface.
2.
Select the appropriate connected valve tile. The unconfigured valve selection screen will pop up. Select the 'Valve
Production Cloning' button. Refer to
Fig. 100: Unconfigured valve selection screen.
3.
On the 'Valve Production Cloning' screen that appears, log in under the OEM access level by selecting the padlock symbol
in the upper right corner of the page. Refer to
Fig.
100.
Fig.
101.
136
Fig.
99.
32-00029—02