Honeywell SV2 Series User Manual page 205

Safety shut-off valves
Table of Contents

Advertisement

Fault
Fault
Category
Description
Security
Installer
password is not
configured.
OEM password
is not
configured.
Installer
account
temporarily
disabled
OEM account
temporarily
disabled
Installer
password
reset feature
temporarily
disabled
OEM password
reset feature
temporarily
disabled
OEM reset
password is not
set.
Solenoid 1 Solenoid 1 relay
fault
SV2 Series Safety Shut-off Valves
V2F, V2V
Detailed Description
Installer password is not
configured (set to default
value).
OEM password is not
configured (set to default
value).
Installer account is
temporarily locked down due
to too many login attempts
with wrong password.
OEM account is temporarily
locked down due to too many
login attempts with wrong
password.
Installer password reset
feature is temporarily
disabled due to too many
unsuccessful reset attempts.
OEM password reset feature
is temporarily disabled due
to too many unsuccessful
reset attempts.
OEM reset password is not
configured although the
feature is enabled.
Solenoid 1 relay was
detected closed during SSOV
cycle test
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Remediation Steps
Configure Installer password to non-
default value.
Configure OEM password to non-default
value.
Wait at least 1 minute before new attempt
to login.
If message is present with no attempts to
login, another device on network might
be trying to login. Find this device and
disable it before trying to login.
Wait at least 1 minute before new attempt
to login.
If message is present with no attempts to
login, another device on network might
be trying to login. Find this device and
disable it before trying to login.
Wait at least 1 minute before new attempt
to reset password.
If message is present with no attempts to
reset password, another device on network
might be trying to reset password. Find
this device and disable it before trying to
reset password.
Wait at least 1 minute before new attempt
to reset password.
If message is present with no attempts to
reset password, another device on network
might be trying to reset password. Find
this device and disable it before trying to
reset password.
Configure OEM reset password OR disable
the OEM password reset feature.
1.) Reset valve and burner management
system, observing valve / burner
operation.
2.) If fault persists, replace valve main
electronics.
205