7.
Perform the Safety Parameter Verification procedure by selecting the Verify Safety Parameters button at the bottom of the
POC tab.
Fig. 141: Safety Parameters Verification page.
8.
After cloning and the above steps are complete, start the valve in the Installer or OEM mode and commission the Pressure
Module Lo-Gas and Hi-Gas settings, if used, to make the valve fully operational:
a. Note that the Fuel/Air valve (V2V models) Base Curve, Correction Curve and Pre-Ignition calibration settings are restored
from the connected FARMOD upon valve power-up.
b. Pressure Module Lo-Gas and Hi-Gas limit settings. Refer to
Navigate to the Setup & Tests menu.
Select the Hi-Gas & Lo-Gas Pressure tile.
Accept the warning statement.
Choose the Hi-Gas or Lo-Gas tab.
Run the burner as specified, allowing the pressure to stabilize. Select the Set Limit button to set the applicable
pressure limit. Repeat with the remaining limit setting.
SV2 Series Safety Shut-off Valves
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Fig.
142.
157