Honeywell SV2 Series User Manual page 65

Safety shut-off valves
Table of Contents

Advertisement

NOTES:
• The SV2 Series valves have internal algorithms that prevent the accidental or intentional removing of the Pressure
Module once the valve has been fully setup and is in use.
If the installed/operational Pressure Module connector is disconnected and reconnected, a 19-Pressure Module
reading fault will occur and can be cleared via the valve reset button.
When a Pressure Module is replaced on the valve, two lockouts will occur; 19-Pressure Module reading fault and 22-
Lo-/Hi-Gas pressure not configured.
The faults cannot be fully cleared until the new Pressure Module is Accepted and the Hi-Gas/Lo-Gas Limits and/or
VPS are re-programmed.
Note that the previously selected Lockout Type for the Hi-Gas/Lo-Gas Limits remain intact as well as the VPS setup,
but the Limit Setpoints are deleted and must be setup in order to make the Limits operational.
• To avoid the 2 lockout conditions mentioned above when replacing a Pressure Module:
BEFORE installing the replacement Pressure Module, disable the Hi-Gas and Lo-Gas Lockout Types and the Valve
Proving Sequence (VPS)
Perform the Verify Safety Parameters procedure to confirm the changes.
Replace the Pressure Module and plug in the electrical connector.
To make the valve operational:
Accept the new Pressure Module and serial number either via the Guided Valve Set Up or the Pressure Module tab in
the Setup & Tests / Settings menus.
If this step is not performed, 3 faults will occur upon entering the Hi-Gas/Lo-Gas Pressure or VPS setup screens. In
order to allow setup functions, the Pressure Module must be Accepted and the valve reset button pushed.
Perform the Pressure Module setup procedures for Hi-Gas Pressure, Lo-Gas Pressure and/or VPS again to ensure
proper setup, since the original Limit Setpoints will be deleted.
Perform the Safety Parameters Verification procedure before the Pressure Module features and the valve will be
operational.
Flanges
Specifications
Models:
MCR37127
Valve size: 1 inch (DN25)
Flange sizes: ½, ¾, 1 and 1 ¼ in NPT or BSPP
DN15, 20, 25, 32
Valve sizes: 1 ½ and 2 in (DN40 and DN50)
Flange sizes: 1, 1 ¼, 1 ½, 2 in NPT or BSPP
DN25, 32, 40, 50
Flange pressure tap sizes & threads:
NPT flanges: 1/8-27" (3mm) NPT. Torque 7±1 Nm (62±9 in-lbf).
BSP flanges: 1/8-28" (3mm) BSP. Torque 1.5±0.15 Nm (13.3±1.3 in-lbf).
Mounting:
1 inch (DN25) valves: Four (4) M5x16 Hex head screws
1 ½, 2 inch (DN40/50) valves: Four (4) M8x20 Hex head screws
Maximum tightening torque
1 inch (DN25) valves: 3.4 Nm (30 in-lbf)
1 ½, 2 inch (DN40/50) valves: 13.5-14.5 Nm (120-128 in-lbf)
Documentation:
32-00028, AB Valve Flange Kits Installation Instructions
32-00036, CD Valve Flange Kits Installation Instructions
SV2 Series Safety Shut-off Valves
V2F, V2V
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
65