Honeywell SV2 Series User Manual page 167

Safety shut-off valves
Table of Contents

Advertisement

SOLA Controller
SOLA CONTROLLER
GROUND
SV2 SERIES VALVE
N
INTERNAL
L1
ELECTRONICS
V1
N
Fig. 149: SOLA with STANDARD Electronics, No External VPS.
SV2 Series Safety Shut-off Valves
V2F, V2V
1
6
POC
VPS
LIMITS
CONTROL
L1
OPTIONAL
ILKIN
ILK WIRING
2
3
ILKOUT
RUN/LOCKOUT
INTERLOCKS
MV1
MV2
V2
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
L1
RM791X
L1
SOLA
PRE-IGNITION
J6
T5
INTERLOCK
LIMIT CONTROL
J6
T3
INPUT
4
5
J5
INTERLOCKS
T1
J5
MAIN VALVE 1/2
T3
167
1
MATCH SV2 SERIES VALVE AND FLAME
SAFEGUARD VOLTAGES.
2
ILK (INTERLOCK) WIRING RUN THROUGH
THE SV2 SERIES VALVE FOR SOLENOID
1
POWER SAVING FEATURE. APPLICABLE
4
TO ALL SV2 SERIES VALVE MODELS.
3
WHEN THE SV2 SERIES VALVE PRESSURE
MODULE IS ENABLED, PROGRAMMED
AND USED FOR LOW GAS PRESSURE
AND HIGH GAS PRESSURE LIMITS, THE
LIMITS ARE INCLUDED IN THE INTERNAL
ILK (INTERLOCK) VALVE STRING. BASIC
(5) ELECTRONICS VALVES DO NOT HAVE
THE ABILITY TO INTERFACE WITH THE
SV2 SERIES VALVE PRESSURE MODULE.
AN EXTERNAL PRESSURE SWITCH MUST
BE USED WITH THESE VALVE MODELS.
4
OBSERVE FLAME SAFEGUARD WIRING
PER ITS MANUAL.
5
IF SOLA INTERNAL OPERATING
CONTROL IS USED, EXTERNAL
CONTROL WIRING NOT APPLICABLE.
6 POC (PROOF OF CLOSURE) MUST BE
FACTORY INSTALLED, INTERNALLY
WIRED AND CALIBRATED.
INDICATES FEEDBACK SENSING OF
RELAY CONTACT STATUS AND LINE
VOLTAGE.
M35594B