Honeywell SV2 Series User Manual

Honeywell SV2 Series User Manual

Safety shut-off valves

Advertisement

Quick Links

SV2 Series Safety Shut-off Valves
VALVE AND HMI/PC TOOL SOFTWARE REVISION 12.01 / 12.01.002 OR LATER
V2F, V2V
USER MANUAL
CONTENTS
CHAPTER 1 INTRODUCTION .........................................................2
DOCUMENTATION ..................................................................................2
APPLICABLE MODELS / VERSIONS.................................................2
FEATURES ..................................................................................................2
WHEN INSTALLING THIS PRODUCT... .............................................2
CYBER SECURITY NOTICE ...................................................................2
VALVES .........................................................................................................3
ACCESSORIES ...........................................................................................3
REPLACEMENT PARTS ..........................................................................4
VALVE SPECIFICATIONS .......................................................................4
Environmental Usage Conditions: .....................................................6
VALVE ACCESSORIES AND REPLACEMENT PARTS ...................8
DIMENSIONAL INFORMATION ..........................................................10
VALVE CAPACITY RATINGS ..................................................................12
VALVE CAPACITY CURVES ....................................................................13
GAS VALVE SIZING ...................................................................................19
CHAPTER 2 VALVE FEATURES ......................................................20
Overview ........................................................................................ 20
Power Saving Feature .............................................................. 21
Valve Interface ............................................................................ 21
INSTALLATION OVERVIEW ..................................................................27
Installation Quick Start Guide ............................................. 29
2. MOUNTING OVERVIEW ..................................................... 32
3. WIRING OVERVIEW ............................................................. 35
CHECKOUT AND OPERATION OVERVIEW .....................................41
5. PROGRAMMING AND SETUP OVERVIEW ................. 44
6. FINAL WIRING AND STATIC CHECKOUT OVERVIEW . 44
CHAPTER 3 COMMUNICATION / CONNECTIVITY ..................46
Introduction ................................................................................. 46
Programming Tools .................................................................. 47
Connectivity Notes ................................................................... 47
Valve Modbus Bias Setup ...................................................... 48
Modbus Addressing ................................................................. 49
CHAPTER 4 ACCESSORIES, FIELD REPLACEMENTS AND
INTELLIGENT FEATURES ...............................................................49
C6097 Pressure Switches ...................................................... 49
Specifications ........................................................ 49
Introduction ............................................................ 50
C6097 Pressure Switch Selection ................. 50
Mounting ................................................................. 51
Programming Tools .................................................................. 51
Specifications ........................................................ 53
Connectivity ............................................................ 54
Safety Features ..................................................... 54
Programming and Setup ................................... 55
Pressure Module........................................................................ 56
Specifications ........................................................ 56
Pressure Module Selection............................... 57
Mounting ................................................................. 58
Theory of Operation ............................................ 59
Low Gas Pressure and High Gas Pressure Operation 60
Valve Proving Sequence (VPS) Operation .. 62
Field Replacement ............................................... 64
Flanges .......................................................................................... 65
Specifications ........................................................ 65
Introduction and Flange Selection ............... 66
Mounting Valve to Flange(s) and Piping .... 66
Replacement Electronics ....................................................... 67
Specifications ........................................................ 67
Introduction and Replacement Assembly Selection 67
Field Replacement ............................................... 68
Replacement Solenoids .......................................................... 69
Specifications ........................................................ 69
Introduction and Replacement Solenoid Selection 69
Field Replacement ............................................... 70
CHAPTER 5 PREMIX TECHNOLOGY ............................................71
Fuel/Air Module ......................................................................... 71
Fuel/Air Accessories ................................................................ 75
Control Possibilities Via Parameter Settings ................ 75
SV2 Series Fuel/Air Valve Theory of Operation ............. 83
CHAPTER 6 ACCESS LEVELS .........................................................112
Password Configuration ......................................................... 112
OEM Password Configuration ............................................. 116
Installer Password Configuration ....................................... 118
Access Levels Assignment .................................................... 124
Installer and OEM Password Reset Procedure ............. 126
CHAPTER 7 VALVE PRODUCTION CLONING ............................133
Unconfigured Valve Procedure ........................................... 136
Valve Configuration without Passwords .......................... 137
Valve Configuration with Passwords ................................. 138
Configured Valve Procedure ................................................. 141
CHAPTER 8 FUEL/AIR RATIO MODULE CHANGE-OUT
PROCEDURE .......................................................................................146
FARMOD Replacement Background ................................. 146
Previously Configured/Used FARMOD procedure ...... 150
CHAPTER 9 VALVE MAIN ELECTRONICS CHANGE-OUT
PROCEDURE .......................................................................................154
Valve Main Electronics Replacement Background ..... 154
New Valve Main Electronics Procedure ........................... 154
CHAPTER 10 .......................................................................................158
CHANGING VALVE / ELECTRONICS ORIENTATION ...................158
Introduction ................................................................................. 158
Electronics Orientation Change Process ........................ 159
LED Orientation Change Process ...................................... 163
Final Wiring Check and Static Checkout ......................... 163
APPENDIX ...........................................................................................164
Burner Control Interface Wiring .......................................... 164
VALVE FAULT CODES .............................................................. 176
TIGHTENING TORQUES ......................................................... 208
MODBUS COMMUNICATION ADDRESSING................. 210
32-00029-02

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SV2 Series

  • Page 1 VALVE CAPACITY RATINGS ..............12 Fuel/Air Accessories ..............75 Control Possibilities Via Parameter Settings ....75 VALVE CAPACITY CURVES ..............13 SV2 Series Fuel/Air Valve Theory of Operation ..... 83 GAS VALVE SIZING ...................19 CHAPTER 6 ACCESS LEVELS ............112 CHAPTER 2 VALVE FEATURES ............20 Password Configuration ............
  • Page 2 CHAPTER 1: INTRODUCTION WHEN INSTALLING THIS PRODUCT… Read these instructions and the appropriate product SV2 Series valves are built on a flexible platform comprising literature carefully. Failure to follow them could damage various functions, voltages, capacities, features and the product or cause a hazardous condition.
  • Page 3 NEMA 1/IP20 or NEMA 4/IP66 with conduit connections enclosure rating, proof of closure switch(es), intelligence level The SV2 Series valve main electronics are side flexible as and electronics orientation. Available features are dependent well as the Pressure Modules. The electronics configuration on release schedule dates.
  • Page 4 Traditional C6097 pressure switches are also compatible Pressure Module or C6097 pressure switch. If the valve is with the SV2 Series valves. C6097 models are SPDT and are not purchased with the required electrical connectors, they available in ¼ in. NPT and flange mount, auto or manual reset,...
  • Page 5 1.5 in (DN40) valve with flanges 1 in/1.25/1.5/2 = DN25/32/40/50: NOTE: The Pressure Module is not a stand-alone product 21.5/25.6/25.9/26.8 and must be used with a SV2 Series valve and thus 2.0 in (DN50) valve with flanges 1 in/1.25/1.5/2 = DN25/32/40/50: is specified as part of the valve approvals.
  • Page 6 Honeywell user interface or the secure Modbus layer USER ACCESS LEVELS A 3-level user access level framework has been implemented into the SV2 Series valves, consisting of the User, Installer and OEM levels. • OEM Read/write rights with the ability to assign read/write parameter groups for the OEM and Installer levels.
  • Page 7 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL VALVE NOMENCLATURE DIGIT #: 15-18 0000 CUSTOMIZATION PRODUCT FAMILY IDENTIFIER 0000: NONE/HONEYWELL V2F: ON/OFF 000X: CUSTOMER SPECIFIC V2V: FUEL/AIR PREMIX PACK TYPE VOLTAGE B: BULK (EU ONLY) 2: 100-120VAC, 50/60HZ U: UNIT 4: 200-240VAC, 50/60HZ...
  • Page 8 SV2 Series Safety Shut-off Valves VALVE ACCESSORIES AND REPLACEMENT PARTS The SV2 Series valve has required and optional accessories for installation, pressure limit operation and set-up. Flanges are required for each valve and must be ordered separately. SV2 Series valves also have field replaceable electronics, modules and solenoids.
  • Page 9 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Category Part Number Description Applicable Model(s) Premix Accessories V2MU0300-010 SV2 Series mixing unit 300kW (1.0MMBTU) All Premix (V2V) models as needed V2MU0500-010 SV2 Series mixing unit 500kW (1.7MMBTU) V2MU0800-010 SV2 Series mixing unit 800kW (2.7MMBTU) V2MU1000-010 SV2 Series mixing unit 1000kW (3.4MMBTU)
  • Page 10 SV2 Series Safety Shut-off Valves NOTE: The purchaser of any SV2 Series valves should keep the original packaging for a period of time, should any returns be required. The original packaging will provide the appropriate cushioning and protection for the valve during shipment back to Honeywell and will ensure no damage occurs to the valve due to handling.
  • Page 11 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL 10-11/32 (263) 7-17/32 (191) 10-33/64 (267) Open Open Fault Self Test Reset Closed Closed 15-15/32 8X M8 (403) SCREWS 2-7/16 (62) 4-5/32 2-15/16 (106) (75) 10-15/32 (266) 3-35/64 (90) 13-7/16 (341) 3-7/64 5-17/64 (133)
  • Page 12 Fig. 6: 1.5/2.0 in (DN40/50) Fuel/air valve with NEMA 4/IP66 enclosure. VALVE CAPACITY RATINGS The SV2 Series valve ratings shown below are for both 4 in. w.c. and 1 in w.c Table 2. Valve Capacity Rating. Valve Capacity Designation / @ 4 in.
  • Page 13 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL VALVE CAPACITY CURVES NOTES: • Capacities for all curves and ratings shown for G20 gas (100% CH4) with specific gravity/relative density of 0.555 at ANSI Z21.21 standard conditions of 15.6°C/60°F and 1013.5mbar / 406.9 in w.c. / 29.2 in Hg / 14.7 PSI pressure.
  • Page 14 SV2 Series Safety Shut-off Valves PRESSURE DROP 1.5 IN (DN40) ON/OFF VALVE CAPACITY CURVES - MBAR - INCHES W.C. 24.9 2.49 10,000 1,000 23,000 28.32 283.2 651.3 NATURAL GAS FLOW - CFH (CUBIC FEET PER HOUR) /HR (METERS CUBED PER HOUR)
  • Page 15 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL PRESSURE DROP -MBAR -INCHES W.C. 2.0 IN (DN50) ON/OFF VALVE CAPACITY CURVES 24.9 2.49 1,000 10,000 38,000 28.32 283.2 1,076 NATURAL GAS FLOW –CFH (CUBIC FEET PER HOUR) –M /HR (METERS CUBED PER HOUR)
  • Page 16 SV2 Series Safety Shut-off Valves PRESSURE DROP 1.0 IN (DN25) PREMIX (V2VXB SERIES) VALVE CAPACITY CURVE TYPICAL -INCHES W.C. -MBAR 401.6 1000 40.16 4.016 0.4016 1000 35.3 3,531 35,315 NATURAL GAS FLOW -M /HR (METERS CUBED PER HOUR) -CFH (CUBIC FEET PER HOUR) VALVE OPERATING RANGE VALVE CAPACITY IS MEASURED WITH 1.0 IN / DN25 FLANGES ASSEMBLED.
  • Page 17 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL PRESSURE DROP 1.5 IN (DN40) PREMIX (V2VXC SERIES) VALVE CAPACITY CURVE TYPICAL -INCHES W.C. -MBAR 401.6 1000 40.16 4.016 0.4016 1000 35.3 3,531 35,315 NATURAL GAS FLOW -M /HR (METERS CUBED PER HOUR)
  • Page 18 SV2 Series Safety Shut-off Valves PRESSURE DROP 2.0 IN (DN50) PREMIX (V2VXD SERIES) VALVE CAPACITY CURVE TYPICAL -INCHES W.C. -MBAR 401.6 1000 40.16 4.016 0.4016 2,000 1000 35.3 3,531 35,315 70,629 NATURAL GAS FLOW -M /HR (METERS CUBED PER HOUR)
  • Page 19 The procedure below along with the valve capacity curves shown in Figs. 7-12 will help to identify the correct valve size for your application. Valve selection may also be accomplished via the SV2 Series valve configuration tool, found at http://www.combustion.honeywell.com/SV2Series. Honeywell gas valve capacities are shown in Figs.
  • Page 20 SV2 Series Safety Shut-off Valves CHAPTER 2 : VALVE FEATURES Overview The SV2 Series valves have two safety shut-off valve seats integrated into a single valve body. They also contain many unique features. Below is an overview of the various valve features. VALVE INTERFACE...
  • Page 21 Power Saving Feature A power saving feature implemented into the SV2 Series valves allows the usage of physically smaller solenoids with less heat generation while saving electrical energy. Run current is reduced via duty-cycling of the voltage applied across the solenoids.
  • Page 22 Refer to the VALVE FAULT CODES section of this manual for detailed fault descriptions. Fault Indicates a Low Gas Pressure fault condition exists when a SV2 Series Pressure Module is used on the valve and programmed. All models with NOTE: The Fault LED will also be lit while this fault is active.
  • Page 23 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Valve Body The valve body is symmetrical on both sides; there are markings molded into the casting including a gas flow directional arrow, valve seat 1 and 2 markings, pressure port access markings (A, B, C, D) and guide posts for mounting to the pressure access ports.
  • Page 24 SV2 Series Safety Shut-off Valves Table 5. Valve Pressure Access Ports. Location Valve Pressure Pressure Port Pressure Usage Access Label Measurement Locations Inlet Flange Inlet Inlet pressure measurement C6097 NPT or Rp mount pressure switch for low gas limit Valve Seat...
  • Page 25 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Open Open Fault Self Test Reset Closed Closed GAS FLOW GAS FLOW DIRECTION DIRECTION INDICATOR INDICATOR PRESSURE ACCESS LOCATION A PRESSURE INDICATOR ACCESS PRESSURE LOCATION D PRESSURE ACCESS INDICATOR ACCESS LOCATION B LOCATION C...
  • Page 26 SV2 Series Safety Shut-off Valves GAS VALVE DIRECTION ARROW O-RING GUIDE LOCATING PIPE ADAPTER HOLES FOR MOUNTING PRESSURE SCREWS MODULE PIPE ADAPTER PRESSURE MODULE PRESSURE OUTLET MODULE PRESSURE MOUNTING SCREWS FUEL AIR MODULE VENT PIPE M35630 Fig. 17: Valve exploded view.
  • Page 27 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL M37160 I=Inlet pressure M=Middle valve seat pressure O=Outlet pressure Fig. 18: Valve Pressure Access Port Locations. INSTALLATION OVERVIEW When Installing This Product… Read installation instructions and the appropriate product literature carefully. Failure to follow them could damage the product or cause a hazardous condition.
  • Page 28 CAUTION The SV2 Series valve should be used with clean gas free of particles bigger than 50 micrometers. To ensure this requirement is met, an external filter element, such as the Honeywell Kromschroeder GFK or similar, can be added to the gas supply line.
  • Page 29 The SV2 Series valve installation steps are illustrated below in the Quick Start Guide. NOTE: This section is an installation overview ONLY. Elaboration of each step is detailed in the SV2 Series Safety Shut-Off Valves Installation Instructions, document 32-00018, which is shipped with each valve and available online.
  • Page 30 B. Remove valve front electrical enclosure cover C. Estimate wiring: • Observe unique line voltage, limits & interlock wiring required for the SV2 Series valves. • More wires may be required than typical valves. D. String wires: •...
  • Page 31 • Valve modbus address + communication speed Instructions. • Low gas pressure B. Power SV2 Series valve and HMI or PC Tool. • High gas pressure C. Complete setup as required and run on-board test procedures as • External VPS (using required.
  • Page 32 Next the valve is mounted to the flange(s) and piping. Depending on the valve size, there are different mounting techniques. Refer to the SV2 Series Valves Installation Instructions, the installation instructions packed with each flange and/or Flanges section of this document.
  • Page 33 • Refer to the Pulse Line Connections and Pulse Line Assembly to FARMOD, Heat Exchanger, Air Pre-Filter and V2MU sections in Chapter 5: Premix Technology for detailed information regarding pulse lines. • The fittings selected by Honeywell from specific brands and types assure free sample flow to and from the SV2 Series fuel/ air ratio premix valve.
  • Page 34 The FARMOD will feel warm after 1 hour of being powered. This is normal. As part of the appliance adjustments during commissioning, the site-specific calibration of the SV2 Series valve/appliance should be performed when the valve/appliance has reached a typical operating temperature for its installation/application in order to minimize the impact of component temperature changes on the fuel/air ratio.
  • Page 35 Pressure Module or C6097 pressure switches. If the valve is not purchased with the required customer wiring connectors, all 5 may be purchased from Honeywell as a bag assembly under part number CONNECTORKIT-000 or purchased externally. For purchasing externally, the appropriate...
  • Page 36 (valve proving sequence) wire routing. SV2 Series valves require line voltage power input at all times to the internal electronics. This is true of all SV2 Series valve models. Interlock wiring is run through all valve models for the solenoid power saving feature.
  • Page 37 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Certain models of the SV2 Series valves also have Modbus interface wiring as well as termination and bias resistor selections. The Modbus interface is used for programming intelligent features and connection to a building automation system.
  • Page 38 SV2 Series Safety Shut-off Valves MAINS CONTROL WIRING PROOF OF CLOSURE SUPPLY GROUND ILK ILK VPS POC MV2 MV1 SOLENOID 1 SOLENOID 2 POC 1 POC 2 MAINS CHASSIS OUT IN SW RS-485 MODBUS – Open Open Fault MODBUS Self Test...
  • Page 39 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Table 7. Factory Wiring Information. Description Purpose Applicable Model(s) SOLENOID 1 Connection from Solenoid 1 to main electronics. Enables powering of solenoid. SOLENOID 2 Connection from Solenoid 2 to main electronics. Enables powering of solenoid.
  • Page 40 NEMA 4/IP66 Enclosures: NOTES: • Use only flexible conduit with the SV2 Series valve NEMA 4/IP66 enclosures. • There are 6 low voltage entry points using M16 x 1.5 cord grips and retaining nuts. • There are 6 entry points with 0.875 in (2.223 cm) holes for use with: –...
  • Page 41 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL NEMA 1 / IP20 Enclosures: 1 Inch / DN25 Valves • Before wiring to connectors, string low and line voltages wires through electrical enclosure rear opening or bottom slot. • Separate the low and line voltage entry points.
  • Page 42 ‘PRESSURE’. F. Valve Modbus Bias Setup The SV2 Series valve can communicate via Modbus RTU communication with any compatible device. Only RTU communications with 1 start bit, 8 data bits, 1 stop bit and no parity is supported.
  • Page 43 • Do not put the system into service until you have satisfactorily completed the Valve Seat Leak Test as detailed in the SV2 Series installation instructions (32-00018), all applicable tests described in the Checkout section of the flame safeguard control manual, and any other tests required by the burner manufacturer.
  • Page 44 SV2 Series Safety Shut-off Valves The procedure outlined in the SV2 Series Valves Installation Instructions is designed to locate and quantify a gas leak. 5. PROGRAMMING AND SETUP OVERVIEW A. Connect Wiring Connect the Modbus wiring per the HMI Tool or PC Tool installation instructions (whichever is used).
  • Page 45 1.54 Nm (11 and 13.63 in-lbf). B. Replace the solenoid cover, if removed during installation, tightening each fastener between 2.2 to 2.35 Nm (19.5 to 20.8 in-lbf). C. Your SV2 Series valve is now ready to use! SV2 Series Safety Shut-off Valves V2F, V2V...
  • Page 46 Modbus addressing. Refer to the Valve Modbus Bias Setup section of this document for more information as well as the reference documents listed at the end of this section for proper SV2 Series valve and Programming Tools Modbus wiring and setup.
  • Page 47 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Programming Tools There are two available models of programming tools for use with the SV2 Series valves with intelligent features. There is an HMI (human machine interface) version and a PC (personal computer) version available.
  • Page 48 1 start bit, 8 data bits, 1 stop bit and no parity is supported. When more than one SV2 Series valve is connected to the HMI or PC Tools or directly connected to a building automation system, the Modbus termination and bias resistors should be adjusted appropriately. The resistors can be found inside the electrical enclosure on the right-hand side.
  • Page 49 CHAPTER 4 : ACCESSORIES, FIELD REPLACEMENTS AND INTELLIGENT FEATURES The SV2 Series valves are built on a flexible modular platform, including modular components that could be added and/or replaced in the field plus several accessories. Additionally, there are intelligent features which can be utilized when certain accessories are used with the SV2 Series valves.
  • Page 50 15, and Fig. 17. The flange mount C6097s cannot be used for low gas pressure on the SV2 Series valves. C6097 NPT versions may be used for low gas pressure mounted via piping and reducing means. C6097 Pressure Switch Selection C6097A models break a control circuit at setpoint on pressure fall and are used for low gas pressure and VPS switches.
  • Page 51 Mounting The flange mount C6097s may be directly mounted on the SV2 Series valves in any of the four (4) positions on the valve body and are keyed for specific mounting orientation. The seal of the flange mount C6097s are designed to cover the center pressure access ports only of each mounting location.
  • Page 52 SV2 Series Safety Shut-off Valves • For detailed C6097 installation instructions when used with the SV2 Series valves, refer to the SV2 Series valves installation instructions, document 32-00018. • You may want to mount the C6097 on the same side as the valve electrical enclosure for easy access when the valve is mounted in the valve train.
  • Page 53 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Programming Tools Fig. 22: Programming Tools. Specifications Models: HMITOOL-000 PCTOOL-000 (comes with PCTOOLKIT-000) Number of Connected Valves: Up to 8 valves wired in daisy chain fashion to a single port HMI Dimensions: Refer to Fig.
  • Page 54 Microsoft Windows 8 Microsoft Windows 8.1 Microsoft Windows 10 32 and 64 bit modes NOTE: An opto-isolated USB to RS-485 converter is recommended for use with the SV2 Series PC Tool to break ground loops. Documentation: 32-00030, HMI Tool Installation Instructions...
  • Page 55 • Fuel/air firing curve Premix/V2V valves The HMI or PC Tools can also be used for SV2 Series valve monitoring, trending, diagnostics and troubleshooting for up to 8 connected valves. Troubleshooting is facilitated by on-board fault messaging with remediation steps. For detailed information on these features, refer to the documents listed under the Specifications section.
  • Page 56 NEMA 4/IP66 with conduit connections versions: -40°F to 150°F / -40°C to 65°C Approvals The Pressure Module is not a stand-alone product and must be used with a SV2 Series valve and thus is specified as part of the valve approvals.
  • Page 57 Introduction The Pressure Module may be used on most SV2 Series valves for multi-function operation. It contains embedded pressure sensors to cover the designated range of the Pressure Module model and can be used for functions including low gas pressure, high gas pressure, VPS (valve proving sequence), leak detection sequence operation and/or pressure monitoring via Modbus.
  • Page 58 SV2 Series Safety Shut-off Valves Mounting The Pressure Module can be mounted in any of the four (4) positions on the valve body and is keyed for specific mounting orientation. The seals of the Pressure Module are designed to cover the center and upper pressure access ports of each mounting location.
  • Page 59 Software algorithms are embedded in the SV2 Series valves to identify not only low and high gas pressure limit faults and VPS test failures, but also when a Pressure Module is un-configured, if there is a reading fault with the Pressure Module, if a pressure limit setting is unusable based on the pressure range of the selected Pressure Module and if the selected Pressure Module is incompatible with the applied valve pressure.
  • Page 60 Since the SV2 Series valves cannot sense a low gas pressure condition prior to opening, it will actively sense and react to the condition once both valve seats are opened. The response time upon sensing the condition is 2.7 seconds after which the valve seats will be closed and the valve will annunciate the fault condition both on the valve face via the LGP LED and the HMI / PC Tool, if connected.
  • Page 61 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL In order to properly program the high and low gas limit settings, the burner must be run so that the embedded pressure sensors can measure the actual pressure that should occur during low fire and high fire conditions, respectively. While the burner is running after stabilization has occurred, the user must select a % over or under the measured operating pressure for the high and low gas limit settings.
  • Page 62 When a VPS sequence is initiated by the external control, the SV2 Series valve intelligent models will automatically determine a VPS sequence is being performed since one valve seat at a time is selectively powered. Accordingly, the valve will initiate its internal leak detection routine, using the attached Pressure Module to measure the pressure rise or decay in the volume between the two safety shut-off valve seats.
  • Page 63 • When utilizing the VPS functionality with the Pressure Module, a NOVV (normally open vent valve) cannot be present unless it is powered during the entire VPS test time. The SV2 Series valves do not provide for cycling the NOVV.
  • Page 64 – PRESSMODx4: 16mbar / 6.4 in wc / 0.23 psi • In case the SV2 Series valve cannot take reliable pressure readings during the external VPS sequence, the SV2 Series valve will lockout. • Very low leakage levels of less than 2 liters/hour (= 33.3 ml/min = 0.07 CFH), which are well below any allowed level, may result due to transient pressure changes caused by the valve balance diaphragm.
  • Page 65 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL NOTES: • The SV2 Series valves have internal algorithms that prevent the accidental or intentional removing of the Pressure Module once the valve has been fully setup and is in use. – If the installed/operational Pressure Module connector is disconnected and reconnected, a 19-Pressure Module reading fault will occur and can be cleared via the valve reset button.
  • Page 66 SV2 Series Safety Shut-off Valves Introduction and Flange Selection Flanges are required to mount each valve and provide connection to standard NPT or BSP gas pipes. There are several available flanges per valve body size. Flange kits designated as AB are for the 1 inch (DN25) valves while flange kits designated as CD are for the 1 ½...
  • Page 67 Any intelligent features utilized are programmed via the Modbus connection to the SV2 Series HMI or PC Tools. Intelligent features include valve Modbus address + communication speed, low gas pressure, high gas pressure, VPS (valve proving sequence), fuel/air ratio, leak detection sequence and metering.
  • Page 68 • More than one power supply disconnect can be involved. CYBER SECURITY NOTICE SV2 Series products contain electronics and software. Care should be taken by the installer / facility management to guard against unauthorized access to the valve and to the programming interface for parameter modification (if applicable).
  • Page 69 Introduction and Replacement Solenoid Selection The SV2 Series individual solenoids can be replaced in the field without replacing the entire valve, should the need arise. Replacement solenoid part numbers are identified by ‘COIL’, followed by the valve body size identifier and applicable voltage.
  • Page 70 Table 15 and/or the model information on the solenoid assembly installed on the valve. • For valve the mechanical and electrical installation, follow the SV2 Series Valve Replacement Electronics installation instruction document, 32-00039, which is packed with the replacement assembly.
  • Page 71 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL CHAPTER 5 : SV2 SERIES PREMIX TECHNOLOGY Fuel/Air Module Specifications Dimensions Refer to Figures 31 and 32. Fig. 31: FARMODxx-000 without insulation. NOTE: FARMOD standoff is approximately 2.5mm from valve body. Fig. 32: FARMODxx-000 with insulation.
  • Page 72 Delta P across FARMOD gas inlet to the Pref outlet Approvals The Fuel/Air Module is not a stand-alone product and must be used with a SV2 Series valve and thus is specified as part of the valve approvals. Amplification Factor Accuracy The achievable accuracy or repeatability of the amplification factor depends on the adjusted value.
  • Page 73 2. ±1.5% of actual sensor reading Fuel/Air Module Introduction The Fuel/Air Module is installed on SV2 Series premix valves for fuel/air regulation (valve model numbers starting with V2V). Each FARMOD contains multiple sensors for accurate measurement of the differential air and gas pressures. Dedicated control electronics and software accurately regulate the fuel/air ratio based on the Fuel/Air Module signals.
  • Page 74 FARMOD is unknown. • The SV2 Series valves have internal algorithms that prevent the accidental or intentional removing of the Fuel Air Ratio Module once the valve has been fully setup and is in use. If the FARMOD cable is disconnected, the valve will lockout.
  • Page 75 Table IMPORTANT: • The fittings selected by Honeywell from specific brands and types assure free sample flow to and from the SV2 Series fuel/ air ratio premix valve. • If any other fittings are used, the sample flow to and from the valve can easily get obstructed and affect the combustion quality.
  • Page 76 SV2 Series Safety Shut-off Valves Preferred Pulse Line Materials and Dimensions Air pressure line: Aluminum or Stainless steel, 8 mm OD x 1 mm thick Gas pressure line: Polyethylene , 8 mm OD x 1.25 mm thick Reference pressure line: Aluminum or Stainless steel, 8 mm OD x 1 mm thick...
  • Page 77 Mixing Units Dedicated SV2 Series premix valve mixing units have been designed to work with and mate to the FARMOD and pulse lines as well as to provide the optimum fuel-air mixing to ensure smooth appliance operation, efficiency and reliability. Refer to Table 18 Fig.
  • Page 78 SV2 Series Safety Shut-off Valves Fig. 35: 1.5-2in/DN40-50 valve to V2MU0500/0800/1000 Fig. 36: 1.5-2in/DN40-50 valve to V2MU2000 Mixing Unit Part Number M5 x 16 mm M8 x 16 mm M8 x 20 mm Nut (M8) Washer V2MU0300 V2MU0500, V2MU0800, V2MU1000 V2MU2000 Table 20.
  • Page 79 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 37: V2MU0300, Dimensional information SV2 Series Safety Shut-off Valves V2F, V2V...
  • Page 80 SV2 Series Safety Shut-off Valves Fig. 38: V2MU0500, V2MU0800, V2MU1000 Dimensional information 32-00029—02...
  • Page 81 The Heat Exchanger Kit, in addition to the heater embedded within the FARMOD, work together to prevent condensate from entering the FARMOD for conditions as indicated above. If the potential of condensate formation exists, it is strongly recommended to install the SV2 Series Heat Exchanger kit, which is available from Honeywell. Refer to Table 21.
  • Page 82 If there is never a risk of condensation, meaning the ambient room temperature is above the combustion air dew point at all times, the complete dehumidification system is not needed. This means adding the additional SV2 Series Heat Exchanger kit is then not needed.
  • Page 83 / O2 (CO2) behavior against the burner load. The ability of the SV2 Series Fuel/Air Ratio control system to store up to 24 burner load-dependable amplification values allows for maximal flexibility in the optimization of the appliance/burner combustion process.
  • Page 84 Note that the S1 and S2b signals do not represent the actual combustion air or gas flow values, but a derivative of the flows. The SV2 Series Fuel/Air Ratio control depends on the ratios of the S1 and S2b signals, which are derived from the stored amplification values at different burner loads during the commissioning of the appliance.
  • Page 85 Pulse Line Assembly to FARMOD, Heat Exchanger, Air Pre-Filter and V2MU The Fuel Air Ratio Module and Honeywell Mixing Units are equipped with 3 pulse line connections for Gas pressure (Port A), Reference pressure (port B) and Air pressure (Port C). Refer to Fig.
  • Page 86 • Refer to the Outdoor Air Installations section for further details regarding pulse lines. NOTE: If the appliance is equipped with a sealed air chamber and the SV2 Series valve with FARMOD is contained in the sealed chamber, it is allowed to not use the air pressure pulse line.
  • Page 87 If the potential of condensate formation exists, it is strongly recommended to install the SV2 Series Heat Exchanger kit, which is available from Honeywell. Refer to Table 21.
  • Page 88 SV2 Series Safety Shut-off Valves Fig. 47: Dehumidification solution working principle. FARMOD Heater The heater is built into the FARMOD design. The Heat Exchanger kit includes a FARMOD insulation shoe, which encases the metal surfaces of the FARMOD. Along with the Heat Exchanger, these items provide a complete dehumidification solution.
  • Page 89 Heat Exchanger Kit The Honeywell heat exchanger can be assembled directly to the V2MU mixing unit. The heat exchanger, in conjunction with the FARMOD embedded heater and insulation shoe, works to reduce the moisture content in the combustion air in hot and humid conditions by cooling the air and condensing moisture out before it enters the pulse line.
  • Page 90 SV2 Series Safety Shut-off Valves NOTES: - V2MU0300-010: If mount the Heat Exchanger directly to the V2MU, rotated inwards and aligned with the V2MU body, there is not enough room to assemble the recommended metal reference pulse line tubing +...
  • Page 91 Heat Exchanger to the V2MU. IMPORTANT: • The SV2 series premix valve and its accessories have been developed to provide an optimum fuel-air ratio performance. • Honeywell cannot guarantee the valve or mixer performance, operation, efficiency or reliability if any non-Honeywell accessories are used with the SV2 Series premix platform.
  • Page 92 The fuel/air ratio valve control offers many settings to tune your appliance to your requirements. Following is an overview of the available settings. The Screen shots were taken from the dedicated SV2 Series HMI/PC Tool user interfaces and are shown in the sequence in which they appear in the Guided Valve Setup.
  • Page 93 52. The stepper motor driven Fuel Control Valve (FCV) is set to a start position after each heat demand and reset of the SV2 Series valve. The first/initial stepper motor start position 2 of the ignition sequence is set with this parameter.
  • Page 94 Refer to Fig. 53. The SV2 Series control offers many possibilities to adjust the ignition behavior to your appliance needs. The following settings and schemes are available. All settings can be adjusted independently. The Base Curve Setup and Correction Curve Setup sections later in this document detail the OEM and Installer amplification factor setup Refer to Fig.
  • Page 95 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 53: Ignition Setup Parameters. First Time Ignition Operation First time ignition operation is typically only performed in the laboratory during development. By selecting a short Ramp Period (and an extra startup delay of 0 = Ignition Period) the control is started almost directly after opening of the two safety valves.
  • Page 96 Ignition Period and Ignition Setpoint Parameters The SV2 Series valve allows the user to make the fuel/air mixture rich or lean during the Ignition Period relative to the amplification setting for the appliance RUN mode or the start load. This occurs AFTER the Ramp Period and Hold On Period timers have expired, when the valve control loop starts to modulate.
  • Page 97 Record Ign. Air Level parameter The SV2 Series valve will check the combustion air level during the ignition phase. To do so, the ignition air level needs to be recorded under normal conditions by checking this box. After modifying the ignition settings that influence the air volume during ignition, like fan speed and flue length / air filters, the ignition air level needs to be recorded / corrected for this new situation.
  • Page 98 SV2 Series Safety Shut-off Valves Fig. 54: Load Saved Curves. 32-00029—02...
  • Page 99 Fig. 55: Load Saved Curves. Base Curve Setup In case no Base Curve has been loaded to the SV2 Series valve, a Base Curve needs to be created, which sets the amplification as a function of the appliance load. Refer to Fig.
  • Page 100 Initial Amplification Factor Set-Up (Set Initial button) To enable the first appliance start, the SV2 Series valve requires an initial amplification value before the first ignition attempt. To do so, set the value by pressing the Lean or Rich up and down arrow buttons and selecting the Set Initial button.
  • Page 101 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL NOTE: If this factor is not entered, the SV2 Series valve will not allow a start-up of the burner. Once the burner is fired, the initial amplification factor can be fine-tuned by pressing the up and down arrow and Set Initial buttons as shown in Fig.
  • Page 102 SV2 Series Safety Shut-off Valves Fig. 57: Correction Curve setup. Adding Points to Create the Correction Curve (Addition button) The Correction Curve needs to be built starting with the Minimum point. To set the Minimum load point, run the appliance at minimum load and set the gain factor for this load by selecting Start Point Commissioning and changing the gain factor with the arrow keys until the excess air level has stabilized at the right level.
  • Page 103 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Deleting Points on the Correction Curve (Deletion button) Single points can be deleted by picking the desired point in the selection box and pushing the Delete single button. The selected point will turn red in the graph and is identified by the X-axis value and the point number counting from left to right.
  • Page 104 By setting the Ignition Period to a longer duration than the safety time of the burner manager control, the SV2 Series control will keep controlling to the ignition-specific amplification factor after the safety time has elapsed until the time of Ignition Period has elapsed.
  • Page 105 The SV2 Series control offers the possibility to enrich the fuel/air mixture during the Ignition Period. The mixture can be made rich during the Ignition Period relative to the amplification setting for the appliance RUN mode or the start load.
  • Page 106 By entering a Ramp Offset value, a Ramp Period value and a Hold On Period value in the appropriate fields as shown in Figs 58-59 (Ignition Setup page), the SV2 Series control controls the gas volume to a lower value at the start of the...
  • Page 107 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL controlled amplification setting can be changed relative to the normal amplification setting (based on the control curves) at the start load (RUN) (as governed by the Ignition Setpoint % parameter) The Ignition Setpoint % defines whether the mixture during the ignition phase is the same, leaner or richer relative to normal operation at ignition load.
  • Page 108 Record Ign. Air Level parameter The SV2 Series valve will check the combustion air level during the ignition phase. To do so, the ignition air level needs to be recorded under normal conditions by checking this box. After modifying the ignition settings that influence the air volume during ignition, like fan speed and flue length / air filters, the ignition air level needs to be recorded / corrected for this new situation.
  • Page 109 • If the minimum and maximum loads are not set, the SV2 Series control will not allow a next startup of the burner if the system is not in commissioning mode. Refer to the Set Min and Set Max buttons in Fig.
  • Page 110 SV2 Series Safety Shut-off Valves • Fig. 65 Fig. 66 show examples of an amplification factor control characteristic Base Curve and Correction Curve with 6 setpoints in the Base Curve and 4 points in the Correction Curve after finishing the setup procedure.
  • Page 111 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL The cloning screens may be accessed one of two ways (refer to Fig. 67): • Selecting the icon of a connected valve and selecting the ‘Valve Production Cloning’ button from the pop-up screen •...
  • Page 112 – Read only rights via HMI/PC Tool and the ability to reset fault codes via valve display. Default Passwords A new SV2 Series valve does not have configured OEM or Installer passwords and must be first accessed via the OEM or Installer default passwords. Default passwords are the same for all valves shipped from Honeywell.
  • Page 113 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL – OEM selects to which parameter groups the Installer will have access to read/write. ₀ Installer can assign/change password if the OEM has granted Installer access to the Installer Security grouping on the Access Level page.
  • Page 114 SV2 Series Safety Shut-off Valves Fig. 69: Fault codes when passwords are un-configured. The following rules must be observed for all passwords: • Minimum twelve characters long • Use a combination of numbers, lower case letters and upper case letters •...
  • Page 115 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 70: Security page for passwords enable/disable, entry, change or reset. Fig. The OEM can choose to enable or disable the OEM and Installer password reset functions on the Security page. Refer to •...
  • Page 116 SV2 Series Safety Shut-off Valves Fig. 71: Change Installer/OEM password dialog box. By selecting the button with the eye symbol, the obscured passwords will be visible. The Key button will not be used. OEM Password Configuration The OEM will need to configure their main password and their reset password if the ‘Enable OEM Password Reset box is checked on the Security page (refer to Fig.
  • Page 117 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 72: Password entry screen. Confirm the new password by selecting the second blank field, entering the password and selecting save again. When the Change Password dialog box reappears (refer to Fig. 73), select Change Password.
  • Page 118 SV2 Series Safety Shut-off Valves Fig. 74: OEM Password Changed confirmation dialog box. It is recommended to select Yes on the Password Changed dialog box, which will bring the user back to the Security page (refer to Fig. 70). a. The user can then log in with the newly created OEM password (see next step).
  • Page 119 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Installer Password Configuration by the OEM Log in using the OEM password. The OEM can login by selecting the padlock symbol in the upper right corner on the Security page. Refer to Fig.
  • Page 120 SV2 Series Safety Shut-off Valves Fig. 78: Installer Password Changed confirmation dialog box. Installer Password Configuration by the Installer Log in using the Installer password. The Installer can login by selecting the padlock symbol in the upper right corner on the Security page.
  • Page 121 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 80: Change Installer password as Installer dialog box with entered password. When the Installer password is changed, the Password Changed dialog box opens. Refer to Fig. Fig. 81: Installer Password Changed confirmation dialog box.
  • Page 122 OEM Reset Password Configuration If enabled, the reset password allows the OEM to reset the current OEM main password back to the Honeywell factory default value. Typically, this would only be performed when the current OEM main password is lost. Once the password is reset, the OEM can then log in and assign a new main password.
  • Page 123 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 83: Change OEM Reset Password dialog box. Type in the current OEM main password in the top box. When OEM password is not configured, the default OEM password is automatically filled in (‘SV2OemKey2017’).
  • Page 124 FARMOD • FAR Correction Curve The Set Access Levels to Default button can only be used when logged in as the OEM to reset all of the settings to the Honeywell default settings as shown in Fig. NOTE: The Access Level parameter grouping assignments are included in the OEM cloning procedure and thus will be copied to new valves with the same access level assignments as the original valve setup being cloned.
  • Page 125 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 86: Access Levels assignment screen with default values. Fig. 87: Access Levels configuration to allow field FARMOD replacement by Installer Table 23. Access Level Groups Category Contents Valve Body • Valve body size Valve General •...
  • Page 126 • The password reset mechanism simply allows the appropriate user to reset the current password(s) back to the Honeywell factory default value(s). Once the password(s) are reset, the user can then log in and assign new password(s). • After reset to the default values, if the passwords are not set to new non-default values, the valve will be in lockout status and will not be operational unless the appropriate user is logged in.
  • Page 127 Installer Password Reset Procedure An installer level 12-character random code is generated at the Honeywell factory, which is only applicable to a particular electronics assembly serial number. That code is placed on a card which is shipped with the valve in the accessory box. It is also shipped with replacement electronics assemblies.
  • Page 128 SV2 Series Safety Shut-off Valves Fig. 89: Security page for passwords entry, change or reset. On the Security page, select the Reset Installer/OEM password button. a. If the user is logged in when this button is selected, the dialog box shown in Fig.
  • Page 129 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 90: Password reset warning dialog box. b. If the user is logged out, the Password Reset dialog box is opened. Refer to Fig. Fig. 91: Reset Password dialog box. Select ‘Installer’ in the dialog box.
  • Page 130 If enabled, the reset password allows the OEM to reset the current OEM main password back to the Honeywell factory default value. Typically, this would only be performed when the current OEM main password is lost. Once the password is reset, the OEM can then log in and assign a new main password.
  • Page 131 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Note that the Installer main password is not reset to the Honeywell factory default by the OEM password reset action. However, at this point the OEM user could choose to change the previously assigned Installer main password without knowing what the previous Installer password is.
  • Page 132 SV2 Series Safety Shut-off Valves Fig. 95: Reset Password dialog box. Select ‘OEM’ in the dialog box. In the blank field, type in the established OEM Reset password. Select the Reset Password button. Refer to Fig. Fig. 96: Reset Password dialog box with entered password.
  • Page 133 Fig. 97: Password Reset acknowledgement dialog box. After successful password reset back to the Honeywell OEM default, the valve will be in lockout status. The user must login using the applicable Honeywell default password level and assign a new OEM main password. Refer to the Default Passwords section and the OEM Password Configuration section of this manual for details.
  • Page 134 SV2 Series Safety Shut-off Valves Fig. 98: Valve Production cloning configuration groups selection. Table 24. Valve configuration groups. Category Contents Description Valve Body • Valve body size + Access Level Valve General • Valve Name + Access Level • Modbus Address + Access Level •...
  • Page 135 3 values will be included in the cloning files of valves with 12.01 firmware or later when using HMI/ PC Tools with 12.01.002 software or later. Contact Honeywell for advice on how to access these settings via the Modbus Editor in the SV2 Series valves user interface tools.
  • Page 136 SV2 Series Safety Shut-off Valves NOTE: If the valve is powered during the safety verification procedure, it will not be un-powered, unless a fault occurs. Depending on whether the attached valve is un-configured or configured and whether the configuration has or does not have passwords, there are slightly different cloning procedures to be followed as detailed next.
  • Page 137 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 101: Valve Production Cloning screen. Select the appropriate valve configuration to load to the valve by pressing the ‘Open’ button beside it (Refer to Fig. 101). The configuration cloning groups page will pop up.
  • Page 138 SV2 Series Safety Shut-off Valves Valve Configuration With Passwords Fig. 103: Valve Production Cloning configuration groups selection, with passwords, ‘Valve Security’ group selected. Fig. 104: Valve Production Cloning configuration groups selection, with passwords, ‘Valve Security’ group selected and OEM configuration password automatically pre-filled.
  • Page 139 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 105: Valve Production Cloning configuration groups selection, with passwords, ‘Valve Security’ group not selected. Select the ‘Load to Valve’ button. As the user interface is sending the selected configuration to the valve, the progress bar pops up to show download progress.
  • Page 140 SV2 Series Safety Shut-off Valves Fig. 108: Safety Parameters Verification page. Perform the Safety Parameters Verification by selecting the ‘Begin’ button. Fig. 109: Safety Parameters Verification completed. 10. Select the ‘Finish Setup’ button to complete the valve cloning procedure. Fig. 110: Setup Complete page.
  • Page 141 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL a. Select the ‘Connect New Valve’ button to connect another valve and/or clone another valve. The user is redirected to the Home page where another valve can be selected for cloning or any connected valve can be selected for viewing status.
  • Page 142 SV2 Series Safety Shut-off Valves Fig. 113: Valve Production cloning selection for configured valve. Select the ‘Valve Production Cloning’ button. Fig. 114: Valve Production Cloning screen. On the ‘Valve Production Cloning’ screen that appears, log in under the OEM access level by selecting the padlock symbol in the upper right hand corner of the page.
  • Page 143 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 115: Valve Production Cloning configuration groups selection, without passwords. Valve Configuration With Passwords Fig. 116: Valve Production Cloning configuration groups selection, with passwords, ‘Valve Security’ group selected. Fig. 117: Valve Production Cloning configuration groups selection, with passwords, ‘Valve Security’ group selected and OEM configuration password automatically pre-filled.
  • Page 144 SV2 Series Safety Shut-off Valves Select the required valve configuration groups. Refer to Table 24 Fig. 117. a. If the ‘Valve Security’ group is checked, the OEM main password must be entered on this page. The OEM main password provided must be the password that was entered when the selected configuration was created. Typically, this password would be specific to a particular valve/appliance configuration and would be the same for valves/appliances of that configuration from an OEM manufacturer in accordance with best practices.
  • Page 145 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 120: Load valve configuration successful completion. 10. Select the ‘OK’ button to proceed to the ‘Safety Parameters Verification’ step. Refer to Fig. 121 Fig. 122. Fig. 121: Safety Parameters Verification page. 11. Perform the Safety Parameter Verification by selecting the ‘Begin’ button.
  • Page 146 SV2 Series Safety Shut-off Valves 12. Select the ‘Home’ wording at the top to go to the Home page (refer to Fig. 99 Fig. 111) or the valve name wording to go to the valve status page (refer to Fig.
  • Page 147 FARMOD is unknown. • The SV2 Series valves have internal algorithms that prevent the accidental or intentional removing of the Fuel Air Ratio Module once the valve has been fully setup and is in use. If the FARMOD cable is disconnected, the valve will lockout.
  • Page 148 SV2 Series Safety Shut-off Valves Fig. 124: Active faults with new FARMOD. Navigate to the Setup & Tests menu and select the Settings tile. See Fig. 125. Fig. 125: Setup & Tests menu. Go to the FARMOD tab and Accept the newly attached FARMOD by pressing the Accept button. Refer to Fig.
  • Page 149 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 126: FARMOD tab, FARMOD not accepted. NOTE: The Disable button should only be used if a FARMOD has been added to an on/off valve by mistake. If it has been added to an on/off valve by mistake, it must be disconnected within 2 hours and the Disable button selected otherwise the main electronics must be replaced to make the valve usable again.
  • Page 150 Fig. Fig. 129: Correction Curve setup. Previously Configured / Used FARMOD Procedure Replace module on valve per instructions in the SV2 Series Valve Fuel Air Ratio Modules installation instruction document, 32-00040, which is packed with the replacement Fuel/Air Module. 32-00029—02...
  • Page 151 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Once the valve is repowered, there will be a FARMOD mismatch active fault present. Refer to Fig. 130. Fig. 130: Active faults with previously configured / used FARMOD. Navigate to the Setup & Tests menu and select the Settings tile. See Fig.
  • Page 152 SV2 Series Safety Shut-off Valves Fig. 132: FARMOD tab, FARMOD not accepted. NOTE: The Disable button should only be used if a FARMOD has been added to an on/off valve by mistake. If it has been added to an on/off valve by mistake, it must be disconnected within 2 hours and the Disable button selected otherwise the main electronics must be replaced to make the valve usable again.
  • Page 153 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 134: Ignition Setup Parameters. The Correction Curve will need to be recommissioned because it is also linked to a specific FARMOD serial number. Select the Correction Curve tab as shown in Fig.
  • Page 154 Base + Correction Curves that were stored in the FARMOD cannot be uploaded to the new main electronics board. • The fuel/air valves (V2V) FARMOD and main electronics CANNOT be replaced at the same time or all Honeywell and OEM factory + field data will be lost, including the valve-specific stepper motor full stroke calibration. If both components must be replaced, the installer must replace 1 at a time.
  • Page 155 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 136: Valve Production Cloning screen. Remove power to the valve and replace electronics assembly per instructions in the SV2 Series Replacement Electronics installation instruction document, 32-00039, which is packed with the replacement electronics assembly.
  • Page 156 SV2 Series Safety Shut-off Valves Once the valve is re-powered, certain premix fuel/air configuration elements, which are specific to a valve + FARMOD are automatically copied from the FARMOD into the new electronics. These include the Base Curve, Correction Curve, motor full stroke and Pre Ign.
  • Page 157 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fig. 140: Proof of Closure Switch tab. Perform the Safety Parameter Verification procedure by selecting the Verify Safety Parameters button at the bottom of the POC tab. Fig. 141: Safety Parameters Verification page.
  • Page 158 1/2 wiring, valve seat 1/2 Open/ Closed LED association and proof of closure 1/2 wiring. The SV2 Series valve electronics and modules are side flexible, regardless of what orientation was ordered from the factory. As explained in the Valve Body section in Chapter 2, the SV2 Series valve bodies are symmetrical on both sides;...
  • Page 159 • More than one power supply disconnect can be involved. IMPORTANT • Use only flexible conduit with the SV2 Series valve NEMA 4/IP66 enclosures • Wiring must comply with all applicable electrical codes, ordinances and regulations. • Wiring must comply with NEC Class 1 (line voltage) wiring.
  • Page 160 SV2 Series Safety Shut-off Valves MAINS CONTROL WIRING SUPPLY PROOF OF CLOSURE GROUND ILK ILK VPS POC MV2 MV1 SOLENOID 1 SOLENOID 2 POC 1 POC 2 MAINS CHASSIS OUT IN SW RS-485 MODBUS – Open Open Fault MODBUS Self Test...
  • Page 161 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Side-mounted components: a. Remove retaining screws for any side-mounted components including the Pressure Module, Fuel/Air Module and C6097 pressure switch(es). b. Make note of mounting location (1 or 2) and access port(s) used (M or O).
  • Page 162 SV2 Series Safety Shut-off Valves Table 25. Proper SOLENOID / POC connection association relative to valve body casting markings. Valve Seat 1 Valve Seat 2 Description SOLENOID 1 SOLENOID 2 Solenoid connector labeling on electronics assembly POC 1 POC 2...
  • Page 163 Final Wiring Check and Static Checkout CAUTION • Cycle the valve several times with the manual fuel shut-off valve(s) closed. Verify that the SV2 Series valve, accessory modules and control system function properly • Test each limit and interlock to ensure system operates correctly as defined in the applicable flame safeguard control manual instructions.
  • Page 164 All SV2 Series valves have a power save feature built in. The ILKIN / ILKOUT circuit is used as a back-up to shut off the valve through the burner control ILK circuit. If for any reason the power save feature fails, the valve internal ILK contact is opened and a fault annunciated.
  • Page 165 At this time, the Pressure Module cannot be used for Lo-Gas / Hi-Gas limit operation on European 7800 SERIES models. No External VPS (Valve Proving System) used; electronics configuration BASIC (5) or STANDARD (6) Wiring between the SV2 Series valve and Honeywell 7800 SERIES, SOLA, 7800 SERIES and ControLinks and SLATE is shown in this section.
  • Page 166 BE USED WITH THESE VALVE MODELS. OBSERVE FLAME SAFEGUARD WIRING MAIN VALVE 1/2 PER ITS MANUAL. FOR THE EC7810, WIRE THE SV2 SERIES VALVE ILK (INTERLOCK) IN SERIES WITH THE LIMITS AND CONTROLLER AS THIS MODEL DOES NOT HAVE AN AIRFLOW SWITCH.
  • Page 167 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL SOLA Controller SOLA CONTROLLER GROUND SV2 SERIES VALVE MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. INTERNAL RM791X ELECTRONICS ILK (INTERLOCK) WIRING RUN THROUGH SOLA THE SV2 SERIES VALVE FOR SOLENOID POWER SAVING FEATURE. APPLICABLE PRE-IGNITION TO ALL SV2 SERIES VALVE MODELS.
  • Page 168 USED FOR LOW GAS PRESSURE AND HIGH GAS PRESSURE LIMITS, THE LIMITS ARE INCLUDED IN THE INTERNAL ILK (INTERLOCK) VALVE STRING. BASIC (5) ELECTRONICS VALVES DO NOT HAVE THE ABILITY TO INTERFACE WITH THE SV2 SERIES VALVE PRESSURE MODULE. AN EXTERAL PRESSURE SWITCH MUST BE USED WITH THESE VALVE MODELS.
  • Page 169 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL SLATE™ SLATE GROUND SV2 SERIES VALVE MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. INTERNAL ILK (INTERLOCK) WIRING RUN THROUGH SLATE ELECTRONICS THE SV2 SERIES VALVE FOR SOLENOID R8001B2001 POWER SAVING FEATURE. APPLICABLE TO ALL SV2 SERIES VALVE MODELS.
  • Page 170 L1 power. Burner controls with independently switched line and neutral voltages will not work as is with the SV2 Series valves and require extra components plus wiring to make them work effectively with the SV2 Series valves.
  • Page 171 • Use a 240/240VAC transformer • ILKIN is only energized if both relays are ON • Transformer may also be used to convert 240/120/24VAC as desired. Match to appropriate SV2 Series valve model (24/120/240VAC). NOTE: EN61558-2-6 specifically requires that the “secondary does not exceed 50 VAC or 120 V ripple-free VDC”, whereas EN61558-2-16 does NOT have such a requirement.
  • Page 172 Pressure Module The SV2 Series valve Pressure Module is used with this scenario with the VPS switch output coming from the SV2 Series electronics. Wiring between the SV2 Series valve and Honeywell 7800 SERIES, 7800 SERIES and ControLinks and SLATE is shown in this section.
  • Page 173 USED FOR LOW GAS PRESSURE AND HIGH GAS PRESSURE LIMITS, THE LIMITS ARE INCLUDED IN THE INTERNAL ILK (INTERLOCK) VALVE STRING. BASIC (5) ELECTRONICS VALVES DO NOT HAVE THE ABILITY TO INTERFACE WITH THE SV2 SERIES VALVE PRESSURE MODULE OR VPS FUNCTIONALITY. AN EXTERNAL PRESSURE SWITCH MUST BE USED WITH THESE VALVE MODELS.
  • Page 174 SV2 Series Safety Shut-off Valves ™ SLATE MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. SLATE ILK (INTERLOCK) WIRING RUN THROUGH THE SV2 SERIES VALVE FOR SOLENOID POWER SAVING FEATURE. APPLICABLE TO ALL SV2 SERIES VALVE MODELS. GROUND SV2 SERIES VALVE...
  • Page 175 L1 power. Burner controls with independently switched line and neutral voltages will not work as is with the SV2 Series valves and require extra components plus wiring to make them work effectively with the SV2 Series valves.
  • Page 176 NOTE: Upon valve reset after a fault, the software will not allow the valve seats to be re-powered by the burner control for 7 seconds to accommodate various flame failure response timings. Table 26. SV2 Series Fault Conditions. Fault Fault...
  • Page 177 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD The bus communication Remove power and shut-off gas supply. communication between the Fuel/Air 1.) Remove valve front electrical enclosure fault Ratio Module and the...
  • Page 178 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD flow The S2a airflow sensor signal 1.) Reset valve and burner management sensor (S2a) out is/was outside the sensor system. of range measuring range (-8000 to 2.) If fault persists, replace Fuel/Air...
  • Page 179 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD The Fuel/Air Ratio stepper If this occurs with fault 34 (FARMOD Warning control valve motor position has reached target (S2b) not reached), it’s an indication...
  • Page 180 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD The Fuel/Air Ratio Module 1.) Accept new Fuel/Air Ratio Module on mismatch has been replaced by a the FARMOD tab in the Setup & Tests used Fuel/Air Ratio Module menu of user interface.
  • Page 181 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air FARMOD rough The Fuel/Air Ratio controlled If this fault occurs with fault 70 (FARMOD target (S2b) not gas pressure was not within...
  • Page 182 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD The Fuel/Air Ratio redundant If this fault occurs directly after Warning target (S2a) not gas pressure signal was not commissioning: indication reached within the control setpoint for SV2 1.) Recommission the 4 points of the...
  • Page 183 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air FARMOD S1 The S1 pre-ignition air If ignition load has changed: pre-ignition air level is below or above the 1.) Recommission light off sequence.
  • Page 184 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air FARMOD light- The Fuel/Air Ratio Module When combined with fault 42 and/or 44 off S2a/S1 ratio S2a/S1 ratio was outside the it’s an indication the fan speed is wrong or commissioned window.
  • Page 185 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air FARMOD light- The Fuel/Air Ratio Module When combined with fault 42 and/or 44 off S2b/S1 ratio S2b/S1 ratio was outside the it’s an indication the fan speed is wrong or commissioned window.
  • Page 186 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD The factory stored data 1.) Replace Fuel/Air Ratio Module. EEPROM inside the Fuel/Air Module is 2.) Accept new Fuel/Air Ratio Module on factory data corrupted, contact your OEM the FARMOD tab in the Setup &...
  • Page 187 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air Control Fuel/Air Control valve is Remove power and shut-off gas supply. Valve stuck. This means that gas 1.) Remove valve front electrical enclosure...
  • Page 188 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air Burner load During curve commissioning, 1.) Check that air duct is clear free of any maximum the S1 threshold is hard- foreign bodies and pollution.
  • Page 189 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD rough The Fuel/Air Ratio Module If this fault occurs directly after Warning target (S2a) not redundant gas pressure commissioning: indication reached signal was not within the for SV2 1.) Recommission the 4 points of the...
  • Page 190 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD Fuel/Air Ratio Module 1.) Reset the valve, monitoring for proper EEPROM write EEPROM write error has operation occurred unexpectedly. 2.) If fault persists replace Fuel/Air Ratio Module.
  • Page 191 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description FARMOD Fuel/Air Ratio Module does 1.) Replace Fuel/Air Ratio Module. Factory not contain valid factory 2.) Accept new Fuel/Air Ratio Module on Calibration data calibration data.
  • Page 192 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Burner load During curve commissioning, 1.) Check that air duct is clear free of any minimum the S1 threshold is hard- foreign bodies and pollution.
  • Page 193 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Fuel/Air S1 raw count During valve idle mode with 1.) Check that air duct is clear free of any MV1 and MV2 closed, the S1 foreign bodies and pollution.
  • Page 194 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Valve Interlock Valve Interlock Out (ILK OUT) 1.) Measure ILK OUT voltage and verify it Out (ILK OUT) terminal energized while does not exist during lockout.
  • Page 195 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Valve Interlock Valve Interlock In (ILK IN) WARNING In (ILK IN) not terminal not energized while Explosion Hazard. energized MV1 and MV2 are energized.
  • Page 196 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Reset button Reset button has been 1.) Attempt valve reset by depressing and fault pressed too long or is stuck. holding button for 2 seconds.
  • Page 197 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description K2 internal relay MV2 internal K2 relay is 1.) Reset valve and attempt system restart. is stuck closed stuck closed unexpectedly 2.) If fault persists, replace valve main electronics board.
  • Page 198 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Phase Incoming Valve incoming L1 VAC to 1.) Reset valve and burner management Warning voltages out of POC or VPS or L1 VAC from system, monitoring for proper operation.
  • Page 199 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description POC (proof of Fault detected in POC 1 Remove power and shut-off gas supply as closure) fault for switch or its connection to necessary.
  • Page 200 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description POC (proof of Proof of closure verification 1.) Ensure the Proof of Closure setup/ closure) of MV1 procedure not completed. acceptance procedure has been not verified performed.
  • Page 201 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description POC 1 (proof POC 1 switch output does Remove power and shut-off gas supply as of closure) not match valve seat 1 necessary.
  • Page 202 SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description POC 2 (proof POC 2 switch output does Remove power and shut-off gas supply as of closure) not match valve seat 2 necessary. incorrect powered/not powered status.
  • Page 203: Table Of Contents

    SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Lo-Gas pressure Low gas pressure below 1.) Reset valve and burner management lockout threshold system, observing burner operation for proper pressures. 2.) Adjust appliance regulator as necessary.
  • Page 204: Pressure Module Not

    SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Pressure Pressure Pressure Module Remove power and shut-off gas supply as Module Module reading communication fault or necessary. fault pressure measurement 1.) Remove valve front electrical...
  • Page 205 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Security Installer Installer password is not Configure Installer password to non- password is not configured (set to default default value. configured. value). OEM password...
  • Page 206: Comments Fault

    SV2 Series Safety Shut-off Valves Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Solenoid Solenoid 1 feedback sensed 1.) Reset valve and burner management 1feeback fault at valve main electronics system, observing valve / burner while MV1 terminal is not operation.
  • Page 207: Warning Indication For Sv2

    SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Fault Fault Detailed Description Remediation Steps Comments Fault Category Description Solenoid 2 Solenoid 2 terminal signal is Remove power and shut-off gas supply as signal fault not valid. Frequency or duty necessary. is out of expected range.
  • Page 208: Warning Indication For Sv2

    Repeat leak detection test. 6.) If fault persists, replace valve. TIGHTENING TORQUES A summary of all tightening torques for the SV2 Series valves and components can be found in Table 2927. Table 27. SV2 Series maximum tightening torques.
  • Page 209 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Category Item Picture Maximum Tightening Torque In-lbf Valve (6) NEMA 4/IP66 wiring Torque hardware enclosure ports, to manufacturer’s recommended (Continued) ½ in (1.27cm) flex conduit requirements (6) NEMA 4/IP66 wiring 4.5-5.1 40-45 ports, ½...
  • Page 210 MODBUS COMMUNICATION ADDRESSING Honeywell SV2 Series valves include a Honeywell specific secure Modbus protocol. Standard Modbus RTU protocol is used, however, safety-related and writable parameters are covered by a secure layer. As a result, they are only writable when accessed using a valid user access level and appropriate user interfaces, which are designed to work with the secure layer.
  • Page 211 SafetyRelayTest A safety relay test performed after power-up or after lockout is cleared. The SV2 Series valve Modbus address space is organized in two segments; holding registers and input registers. Refer to Table 32 for the read and write access function codes.
  • Page 212 SV2 Series Safety Shut-off Valves Table 33. Holding Register Attributes. Holding Meaning Register Bit Register exists Register is writable Safety parameter register Safety parameter register was changed. Need to perform Safety Parameters Verification process. Table 34. Holding Register Mapping. Address...
  • Page 213 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Range Default Model Level Type Value String of chars ended by either ASCII-0 or Pressure end of register array. Standard Pressure Module factory data 62 x Char Module Two chars per register.
  • Page 214 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Range Default Model Level Type Value 0=Disabled 1=Auto reset Low gas pressure (LGP) limit Enum lockout type 2=Manual reset Other value invokes an invalid setup 0=Disabled 1=Auto reset...
  • Page 215 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Range Default Model Level Type Value % of RUN mode target amplification as given by Fuel/Air curve at the ignition load Ignition Setpoint (ignition S1). Determines the target value...
  • Page 216 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Range Default Model Level Type Value 62 x Char 62 x Char 62 x Char 62 x Char 62 x Char 62 x Char 62 x Char 62 x Char...
  • Page 217 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Range Default Model Level Type Value Fuel/air curve name 0 65535 Fuel/air curve name 1 65535 Fuel/air curve name 2 65535 Fuel/air curve name 3 65535...
  • Page 218 SV2 Series Safety Shut-off Valves Table 35. Input Register Mapping Address Type Valve Intelligence Description Data Content Model Levels Type High byte major Valve electronic software revision U8 + U8 Low byte minor Intelligence level identification Standard=0 # of currently active alarms with highest priority...
  • Page 219 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type Valve factory data 62 x Char Main electronics factory data string of characters ended by Valve factory data 62 x Char either ASCII-0 or end of register array.
  • Page 220 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Model Levels Type Current Pressure Module pressure reading. Pressure. Shown in user selected pressure units. See Holding Register 74 for selected units. 0 =Operation is not requested 1 =Powered but communication not established...
  • Page 221 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type 0 =Test has not been performed yet 1 =Test was started 3 =Leakage has been calculated 4 =Test is finished VPS Valve 2 valve status...
  • Page 222 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Model Levels Type Fault code of most recent fault Number Upper 2 bytes Time stamp of most recent fault Lower 2 bytes Upper 2 bytes Cycle count of most recent fault...
  • Page 223 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type Upper 2 bytes Cycle count of 7th previous fault Lower 2 bytes Fault code of 8th previous fault Number Upper 2 bytes Time stamp of 8th previous fault...
  • Page 224 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Model Levels Type Dimensionless - Represents mass flow of air in the appliance. - Can also represent gas flow in the appliance if the Lambda Filtered S1 sensor signal value is held constant.
  • Page 225 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type X-coordinate 6 X-coordinate 7 X-coordinate 8 X-coordinate 9 X-coordinate 10 X-coordinate 11 X-coordinate 12 X-coordinate 13 X-coordinate of CORRECTION fuel/air curve, S1 sensor X-coordinate 14 value.
  • Page 226 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Model Levels Type Fuel/Air curve control valve position 5 Fuel/Air curve control valve position 6 Fuel/Air curve control valve position 7 Fuel/Air curve control valve position 8 Fuel/Air curve control valve position 9...
  • Page 227 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type Fan RPM data point 18 Fan RPM data point 19 Fan RPM data point 20 User entered combustion fan RPM values during Fuel / Air...
  • Page 228 SV2 Series Safety Shut-off Valves Address Type Valve Intelligence Description Data Content Model Levels Type X-coordinate 17 X-coordinate 18 X-coordinate 19 X-coordinate of BASE fuel/air curve, S1 sensor value. X-coordinate 20 Fuel / Air Standard S1 value is dimensionless. X-coordinate 21 -32768 indicates an empty cell.
  • Page 229 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL Address Type Valve Intelligence Description Data Content Model Levels Type Curve related flags. Each bit has its unique meaning: Bit 0 – true indicates that the latest point that has been added to the curve has replaced an existing curve point.
  • Page 230 SV2 Series Safety Shut-off Valves Table 36. VAC Signals Status. Vac Signal Signal State Valve 1 demand Valve 2 demand Interlock string Proof of closure feedback 0=Inactive (off) Solenoid 1 feedback – full power mode 1=Active (on) 2=Invalid Solenoid 2 feedback – full power mode Solenoid 1 feedback –...
  • Page 231 SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL PATENTS The following is a list of granted patents for the SV2 Series valve platform as of January 2018: Country Title Patent Number United States Gas valve with electronic proof of closure system...
  • Page 232 Hauck, Kromschröder and Maxon. To learn more about our products, visit ThermalSolutions.honeywell.com or contact your Honeywell Sales Engineer. For more information on this product and the entire SV2 Series product line, please refer to the SV2 Series User Guide located on our website at Honeywell Process Solutions https://combustion.honeywell.com/sv2...

This manual is also suitable for:

V2fV2v

Table of Contents