Honeywell SV2 Series User Manual page 57

Safety shut-off valves
Table of Contents

Advertisement

Documentation:
32-00017, Pressure Modules Installation Instructions
32-00031, HMI/PC Tool User Manual (detailed programming instructions)
Introduction
The Pressure Module may be used on most SV2 Series valves for multi-function operation. It contains embedded pressure
sensors to cover the designated range of the Pressure Module model and can be used for functions including low gas pressure,
high gas pressure, VPS (valve proving sequence), leak detection sequence operation and/or pressure monitoring via Modbus.
The available functions may be model and mounting location dependent. Refer to
Pressure Modules may only be used on valves with embedded intelligent features; those valves that have an Intelligent Feature
designation of 6 as found in the 9th digit of the valve model number.
• 6 = STANDARD
For an explanation of the above intelligence levels, refer to
Pressure Module Selection
There are four (4) different available pressure ranges for the Pressure Modules and two (2) different versions to match with the
SV2 Series valves NEMA 1/IP20 and NEMA 4/IP66 electrical enclosures. The NEMA 4/IP66 Pressure Module versions have a
cord grip to mate with the valve NEMA 4/IP66 electrical enclosure to maintain the enclosure rating.
Due to the different NEMA/IP ratings and associated temperature range when paired with SV2 Series valves, the applicable
pressure measuring range varies between the NEMA 1/IP20 and NEMA 4/IP66 Pressure Module versions as shown in
Table 11. Available Pressure Modules.
Pressure
Enclosure
Module
Rating
PRESSMOD11-000
PRESSMOD12-000
NEMA 1 / IP20
PRESSMOD13-000
PRESSMOD14-000
PRESSMOD41-000
PRESSMOD42-000
NEMA 4/IP66
PRESSMOD43-000
PRESSMOD44-000
SV2 Series Safety Shut-off Valves
V2F, V2V
Fig. 1
Pressure Module Rating Range
mBar
in w.c.
psi
0.8 - 40
0.3 -16
0.011 - 0.58
2.6 - 160
1.1 - 64
0.038 - 2.32
8.4 - 600
3.4 - 241
0.122 - 8.70
16.8 - 1000
6.7 - 401
0.244 - 14.50
1.3 - 40
0.5 - 16
0.018 - 0.58
3.9- 160
1.6 - 64
0.057 - 2.32
10.5 - 600
4.2 - 241
0.153 - 8.70
21.1 - 1000
8.5 - 401
0.305 - 14.50
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Table 12
Valve nomenclature.
High
Low
Pressure
Pressure
Accuracy
Accuracy
± 1.6 mbar
± 0.03 mbar
± 0.6 in w.c.
± 0.01 in w.c.
± 0.02 psi
± 0.0004 psi
± 6.4 mbar
± 0.11 mbar
± 2.6 in w.c.
± 0.04 in w.c.
± 0.09 psi
± 0.0015 psi
± 24 mbar
± 0.34 mbar
± 9.6 in w.c.
± 0.14 in w.c.
± 0.35 psi
± 0.0049 psi
± 40 mbar
± 0.67 mbar
± 16 in w.c.
± 0.27 in w.c.
± 0.58 psi
± 0.0098 psi
± 1.6 mbar
± 0.05 mbar
± 0.6 in w.c.
± 0.02 in w.c.
± 0.02 psi
± 0.007 psi
± 6.4 mbar
± 0.16 mbar
± 2.6 in w.c.
± 0.06 in w.c.
± 0.09 psi
± 0.0023 psi
± 24 mbar
± 0.42 mbar
± 9.6 in w.c.
± 0.17 in w.c.
± 0.35 psi
± 0.0061 psi
± 0.84 mbar
± 40 mbar
± 0.34 in w.c.
± 16 in w.c.
± 0.0122 psi
± 0.58 psi
57
for details.
Usable
Valve
Temperature
Models
Range
+5°F to +150°F
(-15°C to +65°C)
-40°F to +150°F
(-40°C to +65°C)
Table
11.
All