Motor Potentiometer Macro; Default I/O Connections - ABB ACS350 User Manual

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

90

Motor Potentiometer macro

This macro provides a cost-effective interface for PLCs that vary the speed of the
drive using only digital signals. To enable the macro, set the value of parameter
to 4 (MOTOR POT).
For the parameter default values, see section
on page 142. If you use other than the default connections presented below, see
section

Default I/O connections

max. 500 ohm
1)
If DI3 and DI4 are both active or inactive, the
speed reference is unchanged.
The existing speed reference is stored during
stop and power down.
Application macros
I/O terminals
on page 40.
X1A
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
7
AO
8
GND
2)
9
+24V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
X1B
17
ROCOM
18
RONC
19
RONO
20
DOSRC
21
DOOUT
22
DOGND
Default values with different macros
Signal cable shield (screen)
Not in use by default: 0...10 V
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Not in use by default. 0...10 V
Analog input circuit common
Motor speed value: 0...20 mA
Analog output circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
1)
Speed reference up
1)
Speed reference down
Constant speed 1: parameter
Relay output
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
9902