Parameters – complete descriptions
Index Name/Selection

52 PANEL COMM

5201
STATION ID
1...247
5202
BAUD RATE
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s
5203
PARITY
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
5204
OK MESSAGES
0...65535
5205
PARITY ERRORS
0...65535
5206
FRAME ERRORS
0...65535
5207
BUFFER OVERRUNS Number of characters which overflow the buffer, i.e. number of characters
0...65535
5208
CRC ERRORS
0...65535

53 EFB PROTOCOL

5302
EFB STATION ID
0...247
Description
Communication settings for the control panel port on the drive
Defines the address of the drive. Two units with the same address are not
allowed on-line.
Address
Defines the transfer rate of the link.
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s
Defines the use of parity and stop bit(s). The same setting must be used in all
on-line stations.
No parity bit, one stop bit
No parity bit, two stop bits
Even parity indication bit, one stop bit
Odd parity indication bit, one stop bit
Number of valid messages received by the drive. During normal operation,
this number increases constantly.
Number of messages
Number of characters with a parity error received from the Modbus link. If the
number is high, check that the parity settings of the devices connected on the
bus are the same.
Note: High electromagnetic noise levels generate errors.
Number of characters
Number of characters with a framing error received by the Modbus link. If the
number is high, check that the communication speed settings of the devices
connected on the bus are the same.
Note: High electromagnetic noise levels generate errors.
Number of characters
which exceed the maximum message length, 128 bytes.
Number of characters
Number of messages with an CRC (cyclic redundancy check) error received
by the drive. If the number is high, check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
Number of messages
Embedded fieldbus link settings. See chapter
embedded
fieldbus.
Defines the address of the device. Two units with the same address are not
allowed on-line.
Address
Fieldbus control with
Actual signals and parameters
225
Def, FbEq
1
1 = 1
9.6
1 = 0.1 kbit/s
8 NONE 1
0
1
2
3
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
1
1 = 1