Parameters – short form list
Index
Name/Selection
20
LIMITS
2001
MINIMUM SPEED
2002
MAXIMUM SPEED
2003
MAX CURRENT
2005
OVERVOLT CTRL
2006
UNDERVOLT CTRL
2007
MINIMUM FREQ
2008
MAXIMUM FREQ
2013
MIN TORQUE SEL
2014
MAX TORQUE SEL
2015
MIN TORQUE 1
2016
MIN TORQUE 2
2017
MAX TORQUE 1
2018
MAX TORQUE 2
2019
BRAKE CHOPPER
2020
BRAKE CHOPPER
21
START/STOP
2101
START FUNCTION
2102
STOP FUNCTION
2103
DC MAGN TIME
2104
DC HOLD CTL
2105
DC HOLD SPEED
2106
DC CURR REF
2107
DC BRAKE TIME
2108
START INHIBIT
2109
EMER STOP SEL
2110
TORQ BOOST CURR
2111
STOP SIGNAL DLY
2112
ZERO SPEED DELAY
22
ACCEL/DECEL
2201
ACC/DEC 1/2 SEL
2202
ACCELER TIME 1
2203
DECELER TIME 1
2204
RAMP SHAPE 1
2205
ACCELER TIME 2
2206
DECELER TIME 2
2207
RAMP SHAPE 2
2208
EMER DEC TIME
2209
RAMP INPUT 0
23
SPEED CONTROL
2301
PROP GAIN
2302
INTEGRATION TIME
2303
DERIVATION TIME
2304
ACC COMPENSATION Defines the derivation time for acceleration/(deceleration)
2305
AUTOTUNE RUN
Actual signals and parameters
Description
Drive operation limits.
Defines the allowed minimum speed.
Defines the allowed maximum speed.
Defines the allowed maximum motor current.
Activates or deactivates the overvoltage control of the
intermediate DC link.
Activates or deactivates the undervoltage control of the
intermediate DC link.
Defines the minimum limit for the drive output frequency.
Defines the maximum limit for the drive output frequency.
Selects the minimum torque limit for the drive.
Selects the maximum torque limit for the drive.
Defines minimum torque limit 1 for the drive.
Defines minimum torque limit 2 for the drive.
Defines maximum torque limit 1 for the drive.
Defines maximum torque limit 2 for the drive.
Phased out parameter in sw version 2.51b and later.
Selects the brake chopper control.
Start and stop modes of the motor
Selects the motor starting method.
Selects the motor stop function.
Defines the pre-magnetising time.
Activates the DC Hold or DC braking function.
Defines the DC hold speed.
Defines the DC hold current.
Defines the DC brake time.
Enables the start inhibit function.
Selects the source for the external emergency stop command.
Defines the maximum supplied current during torque boost.
Defines the stop signal delay time when parameter 2102 STOP
FUNCTION is set to SPEED COMP.
Defines the delay for the Zero Speed Delay function.
Acceleration and deceleration times
Defines the source from which the drive reads the signal that
selects between the two ramp pairs.
Defines the acceleration time 1.
Defines the deceleration time 1.
Selects the shape of the acceleration/deceleration ramp 1.
Defines the acceleration time 2.
Defines the deceleration time 2.
Selects the shape of the acceleration/deceleration ramp 2.
Defines the time within the drive is stopped if an emergency stop
is activated.
Defines the source for forcing the ramp input to zero.
Speed controller variables.
Defines a relative gain for the speed controller.
Defines an integration time for the speed controller.
Defines the derivation time for the speed controller.
compensation.
Start automatic tuning of the speed controller.
Def
Custom
0
Eur: 1500 / US:
1800
1.8 ² I2N
ENABLE
ENABLE(TIME)
0
Eur: 50 / US: 60
MIN TORQUE 1
MAX TORQUE 1
-300
-300
300
300
INBUILT
AUTO
COAST
0.3
NOT SEL
5
30
0
OFF
NOT SEL
100
0
0
DI5
5
5
0
60
60
0
1
NOT SEL
10
39204
0
0
OFF