ABB Standard macro

This is the default macro. It provides a general purpose I/O configuration with three
constant speeds. Parameter values are the default values given in chapter
signals and
If you use other than the default connections presented below, see section
terminals

Default I/O connections

1...10 kohm
max. 500 ohm
1)
AI1 is used as a speed reference if vector mode
is selected.
2)
See parameter group
DI3 DI4 Operation (parameter)
0
1
0
1
parameters, starting from page 142.
on page 40.
X1A
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
7
AO
8
GND
4)
9
+24V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
X1B
17
ROCOM
18
RONC
19
RONO
20
DOSRC
21
DOOUT
22
DOGND
12 CONSTANT
0 Set speed through AI1
0 Speed 1 (1202)
1 Speed 2 (1203)
1 Speed 3 (1204)
Signal cable shield (screen)
Output frequency reference: 0...10 V
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Not in use by default. 0...10 V
Analog input circuit common
Output frequency value: 0...20 mA
Analog output circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant speed selection
Constant speed selection
Acceleration and deceleration selection
Relay output
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
3)
0 = ramp times according to parameters
and 2203.
1 = ramp times according to parameters
SPEEDS:
and 2206.
4)
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
Actual
I/O
1)
2)
2)
3)
2202
2205
Application macros
87