Index Name/Selection
LOAD FD SET
USER S1 LOAD
USER S1 SAVE
USER S2 LOAD
USER S2 SAVE
USER S3 LOAD
USER S3 SAVE
9904
MOTOR CTRL MODE Selects the motor control mode.
VECTOR:SPEED
VECTOR:TORQ
SCALAR:FREQ
Description
FlashDrop parameter values as defined by the FlashDrop file. Parameter
view is selected by parameter
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, e.g.
selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User's Manual [3AFE68591074 (English)].
User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 1 macro. Stores the current parameter settings and the motor
model.
User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 2 macro. Stores the current parameter settings and the motor
model.
User 3 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
Save User 3 macro. Stores the current parameter settings and the motor
model.
Sensorless vector control mode.
Reference 1 = speed reference in rpm.
Reference 2 = speed reference in percent. 100% is the absolute maximum
speed, equal to the value of parameter
MINIMUM SPEED if the absolute value of the minimum speed is greater than
the maximum speed value).
Vector control mode.
Reference 1 = speed reference in rpm.
Reference 2 = torque reference in percent. 100% equals nominal torque.
Scalar control mode.
Reference 1 = frequency reference in Hz.
Reference 2 = frequency reference in percent. 100% is the absolute
maximum frequency, equal to the value of parameter
FREQUENCY (or
2007
MINIMUM FREQUENCY if the absolute value of the
minimum speed is greater than the maximum speed value).
1611
PARAMETER VIEW.
2002
MAXIMUM SPEED (or
2008
Def, FbEq
31
0
-1
-2
-3
-4
-5
SCALAR:
FREQ
1
2001
2
3
MAXIMUM
Actual signals and parameters