Maintenance Trig - ABB ACS350 User Manual

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Parameters – complete descriptions
Index Name/Selection
2613
USER DEFINED F2
0.0...500.0 Hz
2614
USER DEFINED U3
0...120% of U
V
N
2615
USER DEFINED F3
0.0...500.0 Hz
2616
USER DEFINED U4
0...120% of U
V
N
2617
USER DEFINED F4
0.0...500.0 Hz
2618
FW VOLTAGE
0...120% of U
V
N
29 MAINTENANCE
TRIG
2901
COOLING FAN TRIG
0.0...6553.5 kh
2902
COOLING FAN ACT
0.0...6553.5 kh
2903
REVOLUTION TRIG
0...65535 Mrev
2904
REVOLUTION ACT
0...65535 Mrev
2905
RUN TIME TRIG
0.0...6553.5 kh
2906
RUN TIME ACT
0.0...6553.5 kh
Description
Defines the second frequency point of the custom U/f curve.
Frequency
Defines the third voltage point of the custom U/f curve at the frequency
defined by parameter
2615
ratio
on page 112.
Voltage
Defines the third frequency point of the custom U/f curve.
Frequency
Defines the fourth voltage point of the custom U/f curve at the frequency
defined by parameter
2617
ratio
on page 112.
Voltage
Defines the fourth frequency point of the custom U/f curve.
Frequency
Defines the voltage of the U/f curve when frequency is equal to or exceeds
the motor nominal frequency
Custom U/f ratio
on page 112.
Voltage
Maintenance triggers
Defines the trigger point for the drive cooling fan run time counter. Value is
compared to parameter
2902
Time. If parameter value is set to zero, the trigger is disabled.
Defines the actual value for the cooling fan run time counter. When
parameter
2901
COOLING FAN TRIG has been set to a non zero value, the
counter starts. When the actual value of the counter exceeds the value
defined by parameter 2901, a maintenance notice is displayed on the panel.
Time. Parameter is reset by setting it to zero.
Defines the trigger point for the motor revolution counter. Value is compared
to parameter
2904
REVOLUTION ACT value.
Millions of revolutions. If parameter value is set to zero, the trigger is
disabled.
Defines the actual value for the motor revolution counter. When parameter
2903
REVOLUTION TRIG has been set to a non zero value, the counter
starts. When the actual value of the counter exceeds the value defined by
parameter 2903, a maintenance notice is displayed on the panel.
Millions of revolutions. Parameter is reset by setting it to zero.
Defines the trigger point for the drive run time counter. Value is compared to
parameter
2906
RUN TIME ACT value.
Time. If parameter value is set to zero, the trigger is disabled.
Defines the actual value for the drive run time counter. When parameter
RUN TIME TRIG has been set to a non zero value, the counter starts. When
the actual value of the counter exceeds the value defined by parameter 2905,
a maintenance notice is displayed on the panel.
Time. Parameter is reset by setting it to zero.
USER DEFINED F3. See section
USER DEFINED F4. See section
(9907
MOTOR NOM FREQ). See section
COOLING FAN ACT value.
Def, FbEq
20
1 = 0.1 Hz
47.5% of U
Custom U/f
1 = 1 V
25
1 = 0.1 Hz
76% of U
Custom U/f
1 = 1 V
40
1 = 0.1 Hz
95% of U
1 = 1 V
0
1 = 0.1 kh
0
1 = 0.1 kh
0
1 = 1 Mrev
0
1 = 1 Mrev
0
1 = 0.1 kh
2905
0
1 = 0.1 kh
Actual signals and parameters
195
N
N
N