ABB ACS350 User Manual page 282

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

282
CODE
FAULT
1000
PAR HZRPM
(6320)
0307
bit 15
1003
PAR AI SCALE
(6320)
0307
bit 15
1004
PAR AO SCALE
(6320)
0307
bit 15
1005
PAR PCU 2
(6320)
0307
bit 15
1007
PAR FBUSMISS
(6320)
0307
bit 15
1009
PAR PCU 1
(6320)
0307
bit 15
1015
PAR CUSTOM U/F
(6320)
0307
bit 15
1017
PAR SETUP 1
(6320)
0307
bit 15
Fault tracing
CAUSE
Incorrect speed/frequency limit
parameter setting
Incorrect analog input AI signal
scaling
Incorrect analog output AO
signal scaling
Incorrect motor nominal power
setting
Fieldbus control has not been
activated.
Incorrect motor nominal speed/
frequency setting
Incorrect voltage to frequency
(U/f) ratio voltage setting.
It is not allowed to use MTAC
encoder module, frequency
input signal and frequency
output signal simultaneously.
WHAT TO DO
Check parameter settings. Check that following
applies:
2001
< 2002,
2007
< 2008,
2001/9908, 2002/9908,
2007/9907
2008/9907
are within range.
Check parameter group
13 ANALOGUE INPUTS
settings. Check that following applies:
1301
< 1302,
1304
< 1305.
Check parameter group
15 ANALOGUE OUTPUTS
settings. Check that following applies:
Check parameter
9909
setting. Following must apply:
1.1 <
(9906
MOTOR NOM CURR ·
NOM VOLT · 1.73 / P
) < 3.0
N
Where P
= 1000 ·
9909
MOTOR NOM POWER (if
N
units are in kW)
or P
= 746 ·
9909
MOTOR NOM POWER (if units
N
are in HP).
Check fieldbus parameter settings. See chapter
Fieldbus control with fieldbus
Check parameter settings. Following must apply:
1 < (60 ·
9907
MOTOR NOM FREQ /
NOM SPEED) < 16
0.8 <
9908
MOTOR NOM SPEED / (120 ·
MOTOR NOM FREQ / Motor poles) < 0.992
Check parameter
2610...2617
Disable frequency output, frequency input or
encoder:
- change transistor output to digital mode (value of
parameter
1804
= DIGITAL), or
- change frequency input selection to other value in
parameter groups