ABB ACS350 User Manual page 71

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive, the drive must be in local control.
Step
Action
1.
• To switch between remote control (REM shown on the status line) and local
control (LOC shown on the status line), press
Note: Switching to local control can be disabled with parameter
LOCK.
The very first time the drive is powered up, it is in remote control (REM) and
controlled through the drive I/O terminals. To switch to local control (LOC) and
control the drive using the control panel, press
how long you press the key:
•If you release the key immediately (the display flashes "Switching to the local
control mode"), the drive stops. Set the local control reference as instructed
on page 73.
•If you press the key for about two seconds, the drive continues as before.
The drive copies the current remote values for the run/stop status and the
reference, and uses them as the initial local control settings.
• To stop the drive in local control, press
• To start the drive in local control, press
.
LOC
REM
1606
. The result depends on
LOC
REM
.
.
Display
LOC
MESSAGE
Switching to the
local control mode.
LOCAL
00:00
The arrow (
status line stops rotating.
The arrow (
status line starts rotating. It
is dotted until the drive
reaches the setpoint.
Control panels
71
or ) on the
or ) on the