ABB ACS350 User Manual page 226

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

226
Parameters – complete descriptions
Index Name/Selection
5303
EFB BAUD RATE
9.6
19.2
38.4
57.6
115.2
5304
EFB PARITY
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
5305
EFB CTRL PROFILE
ABB DRV LIM
DCU PROFILE
ABB DRV FULL
5306
EFB OK MESSAGES
0...65535
5307
EFB CRC ERRORS
0...65535
5310
EFB PAR 10
0...65535
5311
EFB PAR 11
0...65535
5312
EFB PAR 12
0...65535
5313
EFB PAR 13
0...65535
5314
EFB PAR 14
0...65535
5315
EFB PAR 15
0...65535
5316
EFB PAR 16
0...65535
5317
EFB PAR 17
0...65535
Actual signals and parameters
Description
Defines the transfer rate of the link.
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s
Defines the use of parity and stop bit(s) and the data length. The same
setting must be used in all on-line stations.
No parity bit, one stop bit, 8 data bits
No parity bit, two stop bits, 8 data bits
Even parity indication bit, one stop bit, 8 data bits
Odd parity indication bit, one stop bit, 8 data bits
Selects the communication profile. See section
page 258.
ABB Drive limited profile
DCU profile
ABB Drives profile
Number of valid messages received by the drive. During normal operation,
this number increases constantly.
Number of messages
Number of messages with an CRC (cyclic redundancy check) error received
by the drive. If the number is high, check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
Number of messages
Selects an actual value to be mapped to Modbus register 40005.
Parameter index
Selects an actual value to be mapped to Modbus register 40006.
Parameter index
Selects an actual value to be mapped to Modbus register 40007.
Parameter index
Selects an actual value to be mapped to Modbus register 40008.
Parameter index
Selects an actual value to be mapped to Modbus register 40009.
Parameter index
Selects an actual value to be mapped to Modbus register 40010.
Parameter index
Selects an actual value to be mapped to Modbus register 40011.
Parameter index
Selects an actual value to be mapped to Modbus register 40012.
Parameter index
Communication profiles
on
Def, FbEq
9.6
1 = 0.1 kbit/s
8 NONE 1
0
1
2
3
ABB DRV
LIM
0
1
2
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1