3-wire macro

This macro is used when the drive is controlled using momentary push-buttons. It
provides three constant speeds. To enable the macro, set the value of parameter
9902
For the parameter default values, see section
on page 142. If you use other than the default connections presented below, see
section
Note: When the stop input (DI2) is deactivated (no input), the control panel start and
stop buttons are disabled.

Default I/O connections

1...10 kohm
max. 500 ohm
1)
See parameter group
DI3 DI4 Operation (parameter)
0
1
0
1
Application macros
to 2 (3-WIRE).
I/O terminals
on page 40.
X1A
1
2
3
4
5
6
7
8
2)
9
10
11
12
13
14
15
16
X1B
17
18
19
20
21
22
12 CONSTANT
0 Set speed through AI1
0 Speed 1 (1202)
1 Speed 2 (1203)
1 Speed 3 (1204)
Default values with different macros
SCR
Signal cable shield (screen)
AI1
Motor speed reference: 0...10 V
GND
Analog input circuit common
+10V
Reference voltage: +10 VDC, max. 10 mA
AI2
Not in use by default. 0...10 V
GND
Analog input circuit common
AO
Motor speed value: 0...20 mA
GND
Analog output circuit common
+24V
Auxiliary voltage output: +24 VDC, max. 200 mA
GND
Auxiliary voltage output common
DCOM
Digital input common
DI1
Start (pulse
)
DI2
Stop (pulse
)
DI3
Forward (0) / Reverse (1)
DI4
Constant speed selection
DI5
Constant speed selection
ROCOM
Relay output
No fault [Fault (-1)]
RONC
RONO
DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
DOOUT
DOGND
2)
SPEEDS:
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
1)
1)