Parameters – short form list
Index
Name/Selection
4011
INTERNAL SETPNT
4012
SETPOINT MIN
4013
SETPOINT MAX
4014
FBK SEL
4015
FBK MULTIPLIER
4016
ACT1 INPUT
4017
ACT2 INPUT
4018
ACT1 MINIMUM
4019
ACT1 MAXIMUM
4020
ACT2 MINIMUM
4021
ACT2 MAXIMUM
4022
SLEEP SELECTION
4023
PID SLEEP LEVEL
4024
PID SLEEP DELAY
4025
WAKE-UP DEV
4026
WAKE-UP DELAY
4027
PID 1 PARAM SET
41
PROCESS PID SET 2
4101
GAIN
4102
INTEGRATION TIME
4103
DERIVATION TIME
4104
PID DERIV FILTER
4105
ERROR VALUE INV
4106
UNITS
4107
UNIT SCALE
4108
0% VALUE
4109
100% VALUE
4110
SET POINT SEL
4111
INTERNAL SETPNT
4112
SETPOINT MIN
4113
SETPOINT MAX
4114
FBK SEL
4115
FBK MULTIPLIER
4116
ACT1 INPUT
4117
ACT2 INPUT
4118
ACT1 MINIMUM
4119
ACT1 MAXIMUM
4120
ACT2 MINIMUM
4121
ACT2 MAXIMUM
4122
SLEEP SELECTION
4123
PID SLEEP LEVEL
4124
PID SLEEP DELAY
4125
WAKE-UP DEV
4126
WAKE-UP DELAY
Description
Selects a constant value as process PID controller reference,
when parameter 4010 SET POINT SEL value is set to
INTERNAL.
Defines the minimum value for the selected PID reference signal
source.
Defines the maximum value for the selected PID reference
signal source.
Selects the process actual value (feedback signal) for the
process PID controller.
Defines an extra multiplier for the value defined by parameter
4014 FBK SEL.
Defines the source for actual value 1 (ACT1).
Defines the source for actual value ACT2.
Sets the minimum value for ACT1.
Defines the maximum value for the variable ACT1 if an analog
input is selected as a source for ACT1.
See parameter 4018 ACT1 MINIMUM.
See parameter 4019 ACT1 MAXIMUM.
Activates the sleep function and selects the source for the
activation input.
Defines the start limit for the sleep function.
Defines the delay for the sleep start function.
Defines the wake-up deviation for the sleep function.
Defines the wake-up delay for the sleep function.
Defines the source from which the drive reads the signal that
selects between PID parameter set 1 and 2.
Process PID (PID1) control parameter set 2.
See parameter 4001 GAIN.
See parameter 4002 INTEGRATION TIME.
See parameter 4003 DERIVATION TIME.
See parameter 4004 PID DERIV FILTER.
See parameter 4005 ERROR VALUE INV.
See parameter 4006 UNITS.
See parameter 4007 UNIT SCALE.
See parameter 4008 0% VALUE.
See parameter 4009 100% VALUE.
See parameter 4010 SET POINT SEL.
See parameter 4011 INTERNAL SETPNT.
See parameter 4012 SETPOINT MIN.
See parameter 4013 SETPOINT MAX.
See parameter 4014 FBK SEL.
See parameter 4015 FBK MULTIPLIER.
See parameter 4016 ACT1 INPUT.
See parameter 4017 ACT2 INPUT.
See parameter 4018 ACT1 MINIMUM.
See parameter 4018 ACT1 MAXIMUM.
See parameter 4020 ACT2 MINIMUM.
See parameter 4021 ACT2 MAXIMUM.
See parameter 4022 SLEEP SELECTION.
See parameter 4023 PID SLEEP LEVEL.
See parameter 4024 PID SLEEP DELAY.
See parameter 4025 WAKE-UP DEV.
See parameter 4026 WAKE-UP DELAY.
Def
Custom
40
0
100
ACT1
0
AI2
AI2
0
100
0
100
NOT SEL
0
60
0
0.5
SET1
Actual signals and parameters