ABB ACS350 User Manual page 264

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

264
The following tables describe the Status Word content for the DCU profile.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fieldbus control with embedded fieldbus
Name
Value
READY
1
0
ENABLED
1
0
STARTED
1
0
RUNNING
1
0
ZERO_SPEED
1
0
ACCELERATE
1
0
DECELERATE
1
0
AT_SETPOINT
1
0
LIMIT
1
0
SUPERVISION
1
0
REV_REF
1
0
REV_ACT
1
0
PANEL_LOCAL
1
0
FIELDBUS_LOCAL 1
0
EXT2_ACT
1
0
FAULT
1
0
DCU Profile Status Word (par. 0303)
Drive is ready to receive start command.
Drive is not ready.
External Run Enable signal received.
No external Run Enable signal received.
Drive has received start command.
Drive has not received start command.
Drive is modulating.
Drive is not modulating.
Drive is at zero speed.
Drive has not reached zero speed.
Drive is accelerating.
Drive is not accelerating.
Drive is decelerating.
Drive is not decelerating.
Drive is at setpoint. Actual value equals reference value (i.e. is
within tolerance limits).
Drive has not reached setpoint.
Operation is limited by group
Operation is within group
A supervised parameter (group
limits.
All supervised parameters are within limits.
Drive reference is in reverse direction.
Drive reference is in forward direction.
Drive is running in reverse direction.
Drive is running in forward direction.
Control is in control panel (or PC tool) local mode.
Control is not in control panel local mode.
Control is in fieldbus local mode
Control is not in fieldbus local mode.
Control is in EXT2 mode.
Control is in EXT1 mode.
Drive is in a fault state.
Drive is not in a fault state.
Status
20 LIMITS
settings.
20 LIMITS
settings.
32
SUPERVISION) is outside its