Parameters – short form list
Index
Name/Selection
24
TORQUE CONTROL
2401
TORQ RAMP UP
2402
TORQ RAMP DOWN
25
CRITICAL SPEEDS
2501
CRIT SPEED SEL
2502
CRIT SPEED 1 LO
2503
CRIT SPEED 1 HI
2504
CRIT SPEED 2 LO
2505
CRIT SPEED 2 HI
2506
CRIT SPEED 3 LO
2507
CRIT SPEED 3 HI
26
MOTOR CONTROL
2601
FLUX OPT ENABLE
2602
FLUX BRAKING
2603
IR COMP VOLT
2604
IR COMP FREQ
2605
U/F RATIO
2606
SWITCHING FREQ
2607
SWITCH FREQ CTRL
2608
SLIP COMP RATIO
2609
NOISE SMOOTHING
2610
USER DEFINED U1
2611
USER DEFINED F1
2612
USER DEFINED U2
2613
USER DEFINED F2
2614
USER DEFINED U3
2615
USER DEFINED F3
2616
USER DEFINED U4
2617
USER DEFINED F4
2618
FW VOLTAGE
29
MAINTENANCE TRIG
2901
COOLING FAN TRIG
2902
COOLING FAN ACT
2903
REVOLUTION TRIG
2904
REVOLUTION ACT
2905
RUN TIME TRIG
2906
RUN TIME ACT
2907
USER MWh TRIG
2908
USER MWh ACT
30
FAULT FUNCTIONS
3001
AI<MIN FUNCTION
Description
Torque control variables
Defines the torque reference ramp up time.
Defines the torque reference ramp down time.
Speed bands within which the drive is not allowed to operate.
Activates/deactivates the critical speeds function.
Defines the minimum limit for critical speed/frequency range 1.
Defines the maximum limit for critical speed/frequency range 1.
See parameter 2502 CRIT SPEED 1 LO.
See parameter 2503 CRIT SPEED 1 HI.
See parameter 2502 CRIT SPEED 1 LO.
See parameter 2503 CRIT SPEED 1 HI.
Motor control variables
Activates/deactivates the flux optimisation function.
Activates/deactivates the Flux Braking function.
Defines the output voltage boost at zero speed (IR
compensation).
Defines the frequency at which the IR compensation is 0 V.
Selects the voltage to frequency (U/f) ratio below the field
weakening point.
Defines the switching frequency of the drive.
Activates the switching frequency control.
Defines the slip gain for the motor slip compensation control.
Enables the noise smoothing function.
Defines the first voltage point of the custom U/f curve at the
frequency defined by parameter 2611.
Defines the first frequency point of the custom U/f curve.
Defines the second voltage point of the custom U/f curve at the
frequency defined by parameter 2613.
Defines the second frequency point of the custom U/f curve.
Defines the third voltage point of the custom U/f curve at the
frequency defined by parameter 2615
Defines the third frequency point of the custom U/f curve.
Defines the fourth voltage point of the custom U/f curve at the
frequency defined by parameter 2617
Defines the fourth frequency point of the custom U/f curve.
Defines the voltage of the U/f curve when frequency is equal to
or exceeds the motor nominal frequency (9907 MOTOR NOM
FREQ).
Maintenance triggers
Defines the trigger point for the drive cooling fan run time
counter.
Defines the actual value for the cooling fan run time counter.
Defines the trigger point for the motor revolution counter.
Defines the actual value for the motor revolution counter.
Defines the trigger point for the drive run time counter.
Defines the actual value for the drive run time counter.
Defines the trigger point for the drive power consumption
counter.
Defines the actual value of the drive power consumption counter.
Programmable protection functions
Selects how the drive reacts when an analog input signal falls
below the set minimum limit.
Def
Custom
0
0
OFF
0
0
0
0
0
0
OFF
OFF
Varies
80
LINEAR
4
ON
0
DISABLE
USER DEFINED
F1.
10
USER DEFINED
F2.
20
USER DEFINED
F3.
25
USER DEFINED
F4.
40
95% of UN
0
0
0
0
0
0
0
0
NOT SEL
Actual signals and parameters
151