ABB ACS350 User Manual page 172

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

172
Parameters – complete descriptions
Index Name/Selection
DI3
DI4
DI5
START/STOP
COMM
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
1605
USER PAR SET CHG
NOT SEL
DI1
DI2
DI3
DI4
DI5
DI1,2
DI2,3
Actual signals and parameters
Description
See selection DI1.
See selection DI1.
See selection DI1.
Reset along with the stop signal received through a digital input, or by control
panel.
Note: Do not use this option when start, stop and direction commands are
received through fieldbus communication.
Fieldbus interface as the source for the fault reset signal, i.e. control word
0301
FB CMD WORD 1 bit 4 (with ABB drives profile
bit 7). The control word is sent by the fieldbus controller via the fieldbus
adapter or embedded fieldbus (modbus) to the drive. For the control word
bits, see sections
DCU communication profile
communication profile
on page 258.
Reset through inverted digital input DI1 (reset by a falling edge of DI1) or by
control panel
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Enables the change of the User Parameter Set through a digital input. See
parameter
9902
APPLIC MACRO. The change is only allowed when the
drive is stopped. During the change, the drive will not start.
Note: Always save the User Parameter Set by parameter
changing any parameter setting, or reperforming the motor identification. The
last settings saved by the user are loaded into use whenever the power is
switched off and on again or the parameter 9902 setting is changed. Any
unsaved changes will be lost.
Note: The value of this parameter is not included in the User Parameter Sets.
A setting once made remains despite User Parameter Set change.
Note: Selection of User Parameter Set 2 can be supervised via relay output
RO. See parameter
1401
User Parameter Set change is not possible through a digital input. Parameter
Sets can be changed only from control panel.
User Parameter Set control through digital input DI1. Falling edge of digital
input DI1: User Parameter Set 1 is loaded into use. Rising edge of digital
input DI1: User Parameter Set 2 is loaded into use.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
User Parameter Set selection through digital inputs DI1 and DI2. 1 = DI
active, 0 = DI inactive.
DI1
DI2 User Parameter Set
0
0
User Parameter Set 1
1
0
User Parameter Set 2
0
1
User Parameter Set 3
See selection DI1,2.
on page
RELAY OUTPUT 1.
Def, FbEq
3
4
5
7
8
5319
EFB PAR 19
262
and
ABB Drives
-1
-2
-3
-4
-5
NOT SEL
9902
after
0
1
2
3
4
5
7
8