Reference correction examples for DCU profile
With DCU profile the fieldbus reference type can be Hz, rpm or percent. In the
following examples the reference is in rpm.
Setting
COMM+AI1
COMM/1000 + (AI(%) -50%) · (MAX-MIN)
Corrected
reference
1500 rpm
750 rpm
0 rpm
0
Corrected
reference
1500 rpm
1200 rpm
750 rpm
300 rpm
0 rpm
0
When COMM > 0 rpm
AI = 100%
AI = 50%
AI = 0%
150000
750000
AI = 100%
AI = 50%
AI = 0%
750000
150000
Maximum limit is defined by parameter
Minimum limit is defined by parameter
COMM/1000+ (AI(%) -50%) · (MAX-MIN)
COMM
REF
Max limit
Min limit
Max limit
Min limit
COMM
REF
COMM
REF
Min limit
Max limit
Max limit
Min limit
COMM
REF
1105
REF1 MAX /
1104
REF1 MIN /
Fieldbus control with embedded fieldbus
When COMM < 0 rpm
-150000
-750000
AI = 100%
AI = 50%
AI = 0%
-750000
-150000
AI = 100%
AI = 0%
AI = 50%
1108
REF2 MAX.
1107
REF2 MIN.
251
0
0 rpm
-750 rpm
-1500 rpm
Corrected
reference
0
0 rpm
-300 rpm
-750 rpm
-1200 rpm
-1500 rpm
Corrected
reference