ABB ACS350 User Manual page 275

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

CODE
ALARM
2009
DEVICE
OVERTEMP
(4210)
0308
bit 8
2010
MOTOR TEMP
(4310)
0305
bit 9
(programmable fault
function
3005...3009
/ 3503)
2011
UNDERLOAD
(FF6A)
0308
bit 10
(programmable fault
function
3013...3015)
2012
MOTOR STALL
(7121)
0308
bit 11
(programmable fault
function
3010...3012)
2013
AUTORESET
0308
bit 12
2018
PID SLEEP
0309
bit 1
2019
ID RUN
0309
bit 2
2021
START ENABLE 1
MISSING
0309
bit 4
2022
START ENABLE 2
MISSING
0309
bit 5
2023
EMERGENCY
STOP
0309
bit 6
CAUSE
Drive IGBT temperature is
excessive. Alarm limit is
120°C.
Motor temperature is too
high (or appears to be too
high) due to excessive
load, insufficient motor
power, inadequate cooling
or incorrect start-up data.
Measured motor
temperature has exceeded
alarm limit set by
parameter
3503
ALARM
LIMIT.
Motor load is too low due to
e.g. release mechanism in
driven equipment.
Motor is operating in stall
region due to e.g.
excessive load or
insufficient motor power.
Automatic reset alarm
Sleep function has entered
sleeping mode.
Motor Identification Run is
on.
No Start Enable 1 signal
received
No Start Enable 2 signal
received
Drive has received
emergency stop command
and ramps to stop
according to ramp time
defined by parameter
2208
EMER DEC TIME.
WHAT TO DO
Check ambient conditions. See also section
page 291.
Check air flow and fan operation.
Check motor power against unit power.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameters.
Check value of alarm limit.
Check that actual number of sensors corresponds to value
set by parameter
(3501
SENSOR TYPE).
Let motor cool down. Ensure proper motor cooling: Check
cooling fan, clean cooling surfaces, etc.
Check for problem in driven equipment.
Check fault function parameters.
Check motor power against unit power.
Check motor load and drive ratings.
Check fault function parameters.
Check parameter group
31 AUTOMATIC RESET
See parameter groups
40 PROCESS PID SET
1...41 PROCESS PID SET
This alarm belongs to normal start-up procedure. Wait until
drive indicates that motor identification is completed.
Check parameter
1608
START ENABLE 1settings.
Check digital input connections.
Check fieldbus communication settings.
Check parameter
1609
START ENABLE 2 settings.
Check digital input connections.
Check fieldbus communication settings.
Check that it is safe to continue operation.
Return emergency stop push button to normal position.
Derating
settings.
2.
Fault tracing
275