Parameters – complete descriptions
Index Name/Selection
11 REFERENCE
SELECT
1101
KEYPAD REF SEL
REF1(Hz/rpm)
REF2(%)
1102
EXT1/EXT2 SEL
EXT1
DI1
DI2
DI3
DI4
DI5
EXT2
COMM
TIMED FUNC 1
TIMED FUNC 2
TIMED FUNC 3
TIMED FUNC 4
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
1103
REF1 SELECT
KEYPAD
AI1
AI2
Description
Panel reference type, external control location selection and external
reference sources and limits
Selects the type of the reference in local control mode.
Speed reference in rpm. Frequency reference (Hz) if parameter
MOTOR CTRL MODE setting is SCALAR:FREQ.
%-reference
Defines the source from which the drive reads the signal that selects
between the two external control locations, EXT1 or EXT2.
EXT1 active. The control signal sources are defined by parameters
EXT1 COMMANDS and
1103
Digital input DI1. 0 = EXT1, 1 = EXT2.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
EXT2 active. The control signal sources are defined by parameters
EXT2 COMMANDS and
1106
Fieldbus interface as the source for EXT1/EXT2 selection, i.e. control word
0301
FB CMD WORD 1 bit 5 (with ABB Drives profile
bit 11). The control word is sent by the fieldbus controller via the fieldbus
adapter or embedded fieldbus (modbus) to the drive. For the control word
bits, see sections
DCU communication profile
communication profile
on page 258.
Timed EXT1/EXT2 control selection. Timed function 1 active = EXT2, timed
function 1 inactive = EXT1. See parameter group
See selection TIMED FUNC 1.
See selection TIMED FUNC 1.
See selection TIMED FUNC 1.
Inverted digital input DI1. 1 = EXT1, 0 = EXT2.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Selects the signal source for external reference REF1. See section
diagram: Reference source for EXT1
Control panel
Analog input AI1
Analog input AI2
REF1 SELECT.
REF2 SELECT.
5319
on page
262
36 TIMED
on page 99.
Def, FbEq
REF1
9904
1
2
EXT1
1001
0
1
2
3
4
5
1002
7
8
EFB PAR 19
and
ABB Drives
9
FUNCTIONS.
10
11
12
-1
-2
-3
-4
-5
Block
AI1
0
1
2
Actual signals and parameters