96.02

Sine filter support

The control program has a setting that enables the use of ABB sine filters (available
separately). With a sine filter connected to the output of the drive, bit 1 of
Special HW settings
scalar motor control mode, and limits the switching and output frequencies to
• prevent the drive from operating at filter resonance frequencies, and
• protect the filter from overheating.
Contact your local ABB representative before connecting a sine filter from another
manufacturer.
Settings
Parameter
95.01 Special HW settings

Dead-band function

With the Dead-band function, you can freeze the AI reference for a defined area (that
is, dead-band) or ignore a low AI reference caused by possible electromagnetic
interference issues.
AI dead-band value = AI max (12.18/12.28)
In addition, 10% of the dead-band value is added as dead-band hysteresis positive
and negative. This value is internally set in the firmware and cannot be changed.
AI Hysteresis
=
AI dead-band value
Note: AI dead-band (12.110) is applicable for both AI1 and AI2.
boot, or cycle the power. With the lock closed, parameters
visible.
(page 355) and
96.100...96.102
must be switched on. The setting forces the drive to use the
96.02 Pass
96.02 Pass
(page 360).
(page 352).

AI dead-band% (12.110)
10%
Program features 97
code, activate
code. This will again make
95.01