ABB ACS560 Firmware Manual page 151

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Terminal sizes
• (frames R0...R8): 0.14...1.5 mm
• Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)...20 mA, R
input as selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)...20 mA, R
input as selected with parameter 12.25 AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output +24V (X2:10) = 6.0 W (250 mA /
24 V). User can use this source for either of the I/O connections (DI1... DI2- RO1 or
DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
6)
Can be used to set up pressure alarm warning.
7)
Can be used for cold start prevention with connection to 'temperature reached'
output of temperature controller or PLC
8)
Input signal
9)
Output signal
10)
For R0...R2 frames only
11)
The start in forward direction is connected to digital input DI1 and the start/stop in
reverse direction is connected to digital input DI2.
12)
The start is connected to digital input DI1 and the torque reversal is connected to
digital input DI2.
13)
EXT1 is configured for speed control and EXT2 is configured for torque control in
both drive 1 and drive 2.
For information on cable connection and drive operation, see Control Connections in
the hardware manual (3AXD50000044998).
2
(all terminals)
< 500 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage [ 0(2)...10 V, R
in
Control macros 151
> 200 kohm]
in
> 200 kohm]
in