Interlock
The Interlock function can be used to notify the PFC logic on when a motor is not
available. For example, when a motor is under maintenance or due to manual direct-
on-line starting.
When the interlock signal of a motor is in Available status, the motor participates in
the PFC starting sequence. If the signal is in Interlocked status, the motor is excluded
from the PFC sequence.
The interlock function can be defined in the parameter group
Parameter Settings
To enable the PFC macro, navigate to
• Main menu
or
• Main menu
[16] PFC.
The following default values are used for PFC macro:
No.
Value
10.24
7 =
Running
10.27
15 =
Fault (-1)
10.30
46 =
PFC2
12.17
0
12.20
50.0
13.12
2 =
Output frequency
13.18
50.0
19.11
1 =
DI3
19.17
0=No
20.01
1
=In1 Start
20.03
2 =
DI1
20.04
0 =
Always off
20.05
0 =
Always off
20.06
1 =
In1 Start
28.22
0 =
Always off
28.23
0 =
Always off
28.71
0 =
Acc/Dec time 1
30.11
-1500 rpm
31.01
1 =
Inactive (true)
31.02
0 =
Fault
40.07
2 =
On when drive running
40.16
11 =
AI1 percent
40.17
0 =
Not selected
Connection macro
Complete parameter list
 PFC
parameter
No.
Value
20.08
7 =
20.09
0 =
20.12
3 =
20.19
1 =
21.03
0 =
22.11
1 =
22.18
16 =
22.22
0 =
22.23
0 =
22.73
0 =
22.74
0 =
23.11
0 =
28.11
1 =
28.15
16 =
40.19
0 =
40.20
0 =
40.32
2.50
40.33
3.0
76.21
2 =
76.25
2
76.27
2
99.04
0 =
Control macros 131
76 PFC
configuration.
96.04 Macro select
DI6
Always off
DI2
Selected
Coast
AI1 scaled
PID
Always off
Always off
Not used
Not used
Acc/Dec time 1
AI1 scaled
PID
Not selected
Not selected
PFC
Scalar
