224 Parameters
No.
Name/Value
Enabled (init at stop
/power-up)
Enabled (resume
always)
Enabled (init to
actual)
22.72
Motor
potentiometer initial
value
-32768.00...
32767.00
22.73
Motor
potentiometer up
source
Not used
Not used
DI1
DI2
DI3
DI4
DI5
DI6
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
Description
When enabled, the motor potentiometer first adopts the value
defined by parameter
22.72 Motor potentiometer initial
The value can then be adjusted from the up and down
sources defined by parameters
source
and
22.74 Motor potentiometer down
A stop or a power cycle will reset the motor potentiometer to
the initial value (22.72).
As
Enabled (init at stop
potentiometer value is retained over a stop or power cycle.
Whenever another reference source is selected, the value of
the motor potentiometer follows that reference. After the
source of reference returns to the motor potentiometer, its
value can again be changed by the up and down sources
(defined by
22.73
and 22.74).
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter
potentiometer
function.
Initial value for motor potentiometer.
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
Note: Motor potentiometer function up/down source control
speed or frequency from zero to maximum speed or
frequency. The running direction can be changed with
parameter
20.04 Ext1 in2
Motor potentiometer macro
Not used
Not used
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
22.73 Motor potentiometer up
source.
/power-up), but the motor
source. See the figure in section
on page 111.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 273).
(see page 273).
(see page 273).
(see page 266).
(see page 266).
(see page 266).
Def/FbEq16
1
value.
2
3
0.00
22.71 Motor
1 = 1
Not used
0
1
2
3
4
5
6
7
18
19
20
24
25
26
on page 162). -