Terminal sizes
• (frames R0...R8): 0.14...1.5 mm
• Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)...20 mA, R
input as selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)...20 mA, R
input as selected with parameter 12.25 AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output +24V (X2:10) = 6.0 W (250 mA /
24 V). User can use this source for either of the I/O connections (DI1... DI2- RO1 or
DI3...DI6 - RO2
RO3).
~
4)
The constant speed is set based on the following combination of sources:
Source defined
by
No.22.22
0
1
0
0
5)
Connected with jumpers at the factory.
6)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
7)
Input signal
8)
Output signal
9)
For R0...R2 frames only
In addition, some inputs and settings are set automatically as follows:
No.
Name (Input/Setting)
20.01
Ext1 commands
21.03
Stop mode
23.11
Ramp set selection
23.12
Acceleration time 1
23.13
Deceleration time 1
99.04
Motor control mode
For information on cable connection and drive operation, see Control Connections in
the Hardware manual (3AXD50000044998).
2
< 500 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage [ 0(2)...10 V, R
in
Source
Source defined
defined by
by
No.22.23
0
0
0
0
1
0
0
1
(all terminals)
Constant speed
par.22.24
active
Set speed through AI1
Constant speed 1
Constant speed 2
Constant speed 4
Value
4 =
In1P Start; In2 Stop
1 =
Ramp
0 =
Acc/Dec time 1
300 s
300 s
1 =
Vector
Control macros 145
> 200 kohm]
in
> 200 kohm]
in
Value
-
600
900
1480