ABB ACS560 Firmware Manual page 267

General purpose drives
Table of Contents

Advertisement

No.
Name/Value
Abs high
Both
Abs both
Hysteresis
32.06
Supervision 1
action
No action
Warning
Fault
Fault if running
32.07
Supervision 1
signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Inverter
temperature
Process PID output
Process PID
feedback
Process PID
setpoint
Process PID
deviation
Other
32.08
Supervision 1 filter
time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474836.00...
21474836.00
Description
Action is taken whenever the absolute value of the signal
rises above its (absolute) high limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Action is taken whenever the signal rises above the value
defined by the high limit + 0.5 hysteresis. The action is
deactivated when the signal falls below the value defined by
the low limit - 0.5 hysteresis.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B0 Signal supervision 1
Drive trips on fault
80B0 Signal supervision
If running, the drive trips on fault
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 165).
01.10 Motor torque
(page 165).
01.11 DC voltage
(page 165).
01.14 Output power
(page 166).
12.11 AI1 actual value
(page 189).
12.21 AI2 actual value
(page 191).
05.11 Inverter temperature
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
Source selection (see
Terms and abbreviations
Defines a filter time constant for the signal monitored by
signal supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
is generated.
1.
80B0 Signal supervision
(page 165).
(page 165).
(page 171).
(page 295).
(page 295).
(page 295).
(page 295).
on page 162). -
Parameters 267
Def/FbEq16
4
5
6
7
No action
0
1
2
1.
3
Frequency
0
1
3
4
6
7
8
9
10
23
24
25
26
27
0.000 s
1000 = 1 s
0.00
-