Supervision - ABB ACS560 Firmware Manual

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

266 Parameters
No.
Name/Value
31.36
Aux fan fault
function
Fault
Warning
No action
32

32 Supervision

32.01
Supervision status
Bit
Name
0
Supervision 1 active
1
Supervision 2 active
2
Supervision 3 active
3
Supervision 4 active
4
Supervision 5 active
5
Supervision 6 active
6...15
Reserved
0b0000...0b1111
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Description
Selects how the drive reacts when an auxiliary fan problem is
detected.
Certain drive types (especially those protected to IP55) have
an auxiliary fan built into the front cover as standard.
If it is necessary to operate the drive without the front cover
(for example, during commissioning), you can set the
parameter to value No action within two minutes from power-
up to temporarily suppress the fault or warning. Return the
value to Fault or Warning afterwards.
This parameter is applicable only for frames R3 or larger.
On frame sizes R3...R5, the auxiliary fan is attached to
connector X10 and on frame sizes R6 and larger to connector
X16.
The drive trips on fault
5081 Auxiliary fan
The fault is suppressed for two minutes after power-up.
The drive generates a warning
The warning is suppressed for two minutes after power-up.
No action taken
Configuration of signal supervision functions 1...6.
Six values can be chosen to be monitored; a warning or fault
is generated whenever predefined limits are exceeded.
See also section
Signal supervision
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note: This word is independent of the drive actions defined
by parameters 32.06, 32.16, 32.26, 32.36,
Description
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
Signal supervision status word.
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter 32.07) is compared
to its low and high limits
action to be taken when the condition is fulfilled is selected by
32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its low limit.
Action is taken whenever the signal rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit.
broken.
A582 Auxiliary fan
(page 93).
32.46
32.07
is outside its limits.
32.17
is outside its limits.
32.27
is outside its limits.
32.37
is outside its limits.
32.47
is outside its limits.
32.27
is outside its limits.
(32.09
and
32.10
respectively). The
Def/FbEq16
Warning
0
missing.
1
2
0b000
and 32.56.
1 = 1
Disabled
0
1
2
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents