Fba A Data Out; Embedded Fieldbus - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

332 Parameters
No.
Name/Value
Other
...
...
52.12
FBA A data in12
53

53 FBA A data out

53.01
FBA A data out1
None
CW 16bit
Ref1 16bit
Ref2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
CW2 16bit
Other
...
...
53.12
FBA A data out12
58

58 Embedded fieldbus

58.01
Protocol enable
None
Modbus RTU
58.02
Protocol ID
58.03
Node address
0...255
58.04
Baud rate
Autodetect
4.8 kbps
9.6 kbps
Description
Source selection (see
Terms and abbreviations
...
See parameter
52.01 FBA A data in1.
Selection of data to be transferred from fieldbus controller to
drive through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
53.01...53.12
the fieldbus controller to the drive through fieldbus adapter A.
None.
Control Word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Control Word (32 bits)
Reference REF1 (32 bits)
Reference REF2 (32 bits)
Control Word 2 (16 bits)
Source selection (see
Terms and abbreviations
...
See parameter
53.01 FBA A data
Configuration of the embedded fieldbus (EFB) interface.
See also chapter
Fieldbus control through the embedded
fieldbus interface (EFB)
Enables/disables the embedded fieldbus interface and
selects the protocol to use.
None (communication disabled).
Embedded fieldbus interface is enabled and uses the Modbus
RTU protocol.
Displays the protocol ID and revision.
This parameter is read-only.
Protocol ID and revision.
Defines the node address of the drive on the fieldbus link.
Values 1...247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Node address (values 1...247 are allowed).
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Baud rate detected automatically
4.8 kbit/s.
9.6 kbit/s.
on page 162). -
select data to be transferred from
on page 162). -
out1.
(page 437).
settings).
settings).
Def/FbEq16
...
None
None
0
1
2
3
11
12
13
21
...
None
None
0
1
-
1 = 1
1
58.06
1 = 1
19.2 kbps
58.06
0
1
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents