Notes
1)
The signal source is powered externally. See the manufacturer's instructions. To
use sensors supplied by the drive aux. voltage output, see chapter Electrical
installation, section Connection examples of two-wire and three-wire sensors in the
Hardware manual of the drive.
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
3)
Connected with jumpers at the factory.
4)
Total load capacity of the auxiliary voltage output +24V (X2:10) = 6.0 W (250 mA /
24 V). User can use this source for either of the I/O connections (DI1... DI2- RO1 or
DI3...DI6 - RO2
RO3).
~
5)
Input signal
6)
Output signal
7)
For R0...R2 frames only
For information on cable connection and drive operation, see Control Connections in
the hardware manual (3AXD50000044998).