188 Parameters
No.
Name/Value
11.43
Freq in 1 max
0 ... 16000 Hz
11.44
Freq in 1 at scaled
min
-32768.000...
32767.000
11.45
Freq in 1 at scaled
max
-32768.000...
32767.000
12

12 Standard AI

12.02
AI force selection
Bit
Value
0
1 = Force AI1 to value of parameter
1
1 = Force AI2 to value of parameter
2...15
Reserved
0b000...0b1111
12.03
AI supervision
function
No action
Fault
Warning
Last speed
Description
Defines the maximum for the frequency actually arriving at
frequency input 1 (DI5 or DI6 when it is used as a frequency
input). See parameter
11.42 Freq in 1
Maximum frequency for frequency input 1 (DI5 or DI6).
Defines the value that is required to correspond internally to
the minimum input frequency defined by parameter
Freq in 1
min. See diagram at parameter
Value corresponding to minimum of frequency input 1.
Defines the value that is required to correspond internally to
the maximum input frequency defined by parameter
Freq in 1
max. See diagram at parameter
Value corresponding to maximum of frequency input 1.
Configuration of standard analog inputs.
The true readings of the analog inputs can be overridden for
e.g. testing purposes. A forced value parameter is provided
for each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: AI filter times (parameters
12.26 AI2 filter
time) have no effect on forced AI values
(parameters
12.13 AI1 forced value
value).
Note: Boot and power cycle reset the force selections
(parameters
12.02
and 12.03).
Forced values selector for analog inputs AI1 and AI2.
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the
limits. For example, if the maximum limit for the input is
7.000 V, the maximum limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by
parameter
12.04 AI supervision
No action taken.
Drive trips on
80A0 AI
supervision.
Drive generates an
A8A0 AI supervision
Drive generates a warning
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
min.
11.42 Freq in 1
11.42 Freq in 1
12.16 AI1 filter time
and
12.23 AI2 forced
12.13 AI1 forced
value.
12.23 AI2 forced
value.
selection.
warning.
(A8A0 AI
supervision) and freezes
Def/FbEq16
16000 Hz
1 = 1 Hz
0.000
11.42
min.
1 = 1
50.000
11.43
min.
1 = 1
0b0000
and
1 = 1
No action
0
1
2
3

Hide quick links: