ABB ACS560 Firmware Manual page 419

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Warning / Aux. code
(aux code visible only
Code
on assistant control
(hex)
panel and drive
composer)
A7C1
FBA A communication
Programmable warning:
50.02 FBA A comm loss
func
A7CE
EFB comm loss
Programmable warning:
58.14 Communication loss
action
A7EE
Panel loss
Programmable warning:
49.05 Communication loss
action
A88F
Cooling fan
A8A0
AI supervision
0001 – AI1 less minimum
0002 – AI1 greater maximum
A8A1
RO life warning
A8A2
RO toggle warning
Cause
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Communication break in
embedded fieldbus (EFB)
communication.
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Maintenance timer limit
exceeded.
Analog signal is beyond limits.
The relay has changed states
more than the recommended
number of times.
0001 Relay output 1
0002 Relay output 2
0003 Relay output 3
The relay output is changing
states faster than
recommended, eg. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
0001 Relay output 1
0002 Relay output 2
What to do
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
Fieldbus adapter
settings,
52 FBA A data in
data
out.
Check cable connections.
Check if communication master is able to
communicate.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Check PC tool or control panel
connection.
Check control panel connector.
Check mounting platform if being used.
Disconnect and reconnect the control
panel.
Replace the drive cooling fan.
Parameter
05.04 Fan on-time counter
shows the running time of the cooling
fan.
Check the signal level, input wiring, and
the defined limits.
0003 – AI2 less minimum
0004 – AI2 greater maximum
Change the control board or stop using
the relay output.
Change the control board or stop using
relay output 1.
Change the control board or stop using
relay output 2.
Change the control board or stop using
relay output 3.
Replace the signal connected to the relay
output source with a less frequently
changing signal.
Select a different signal with parameter
10.24 RO1
source.
Select a different signal with parameter
10.27 RO2
source.
Fault tracing 419