192 Parameters
No.
Name/Value
mA
12.26
AI2 filter time
0.000...30.000 s
12.27
AI2 min
0.000...22.000
12.28
AI2 max
0.000...22.000 mA
12.29
AI2 scaled at AI2
min
-32768.000...
32767.000
12.30
AI2 scaled at AI2
max
-32768.000...
32767.000
12.101 AI1 percent value
0.00...100.00%
12.102 AI2 percent value
0.00...100.00%
Description
Milliamperes.
Defines the filter time constant for analog input AI2. See
parameter
12.16 AI1 filter
Filter time constant.
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
Minimum value of AI2.
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
Maximum value of AI2.
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
(Changing the polarity settings of
effectively invert the analog input.)
AI
scaled
12.101
12.27
Real value corresponding to minimum AI2 value.
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
See the drawing at parameter of
Real value corresponding to maximum AI2 value.
Value of analog input AI1 in percent of AI1 scaling
max
-
12.17 AI1
min).
AI1 value
Value of analog input AI2 in percent of AI2 scaling
max
-
12.27 AI2
min).
AI2 value
time.
12.27 AI2
12.29
and
12.101
(12.22)
12.28
12.29
12.28 AI2
12.29 AI2 scaled at AI2
Def/FbEq16
10
0.100 s
1000 = 1 s
4.000 mA
1000 = 1 unit
20.000 mA
1000 = 1 unit
0.000
min.
can
AI
(12.21)
in
1 = 1
50.000
max.
min.
1 = 1
(12.18 AI1
0
100 = 1%
(12.28 AI2
0
100 = 1%