No.
Name/Value
47.14
Data storage 4
int32
-2147483648...
2147483647
47.21
Data storage 1
int16
-32768...32767
47.22
Data storage 2
int16
-32768...32767
47.23
Data storage 3
int16
-32768...32767
47.24
Data storage 4
int16
-32768...32767
49
49 Panel port
communication
49.01
Node ID number
1...32
49.03
Baud rate
38.4 kbps
57.6 kbps
86.4 kbps
115.2 kbps
230.4 kbps
49.04
Communication
loss time
0.3...3000.0 s
49.05
Communication
loss action
No action
Fault
Last speed
Description
Data storage parameter 12.
32-bit data.
Data storage parameter 17.
16-bit data.
Data storage parameter 18.
16-bit data.
Data storage parameter 19.
16-bit data.
Data storage parameter 20.
16-bit data.
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note: For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
Node ID.
Defines the transfer rate of the link.
38.4 kbit/s.
57.6 kbit/s.
86.4 kbit/s.
115.2 kbit/s.
230.4 kbit/s.
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
action
is taken.
Panel/PC tool communication timeout.
Selects how the drive reacts to a control panel (or PC tool)
communication break.
No action taken.
Drive trips on
7081 Control panel
Drive generates an
A7EE Panel loss
speed to the level the drive was operating at. The speed is
determined on the basis of actual speed using 850 ms low-
pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
49.05 Communication loss
loss.
warning and freezes the
Parameters 323
Def/FbEq16
0
-
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
1
1 = 1
115.2 kbps
1
2
3
4
5
10.0 s
10 = 1 s
Fault
0
1
2

Hide quick links: