ABB ACS560 Firmware Manual page 433

General purpose drives
Table of Contents

Advertisement

Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
8002
ULC overload fault
8009
Current limit
80A0
AI supervision
Programmable fault:
12.03 AI supervision
function
1 – AI1LessMIN
2 – AI1GreaterMAX
80B0
Signal supervision 1
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
80B3
Signal supervision 4
(Editable message text)
Programmable fault:
32.36 Supervision 4 action
(aux
Cause
004 Underload occurred between
speed point
37.14 ULC speed
table point 4
and
speed table point
User load curve: Signal has
been too long over the
overload curve.
001 Overload occurred between
speed point
37.11 ULC speed
table point 1
and
speed table point
002 Overload occurred between
speed point
37.12 ULC speed
table point 2
and
speed table point
003 Overload occurred between
speed point
37.13 ULC speed
table point 3
and
speed table point
004 Overload occurred between
speed point
37.14 ULC speed
table point 4
and
speed table point
Motor actual current exceeded
the limit defined in parameter
30.17 Maximum
current.
An analog signal is outside the
limits specified for the analog
input
Fault generated by the signal
supervision function 1.
Fault generated by the signal
supervision function 2.
Fault generated by the signal
supervision function 3.
Fault generated by the signal
supervision function 4.
What to do
Check the load.
37.15 ULC
5.
See parameter
actions.
Check the load.
37.12 ULC
2.
Check the load.
37.13 ULC
3.
Check the load.
37.14 ULC
4.
Check the load.
37.15 ULC
5.
Reduce the motor load. Check for any
jam or stall in motor.
See parameter
Check signal level at the analog input.
Check the auxiliary code.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
Standard
3 – AI2LessMIN
4 – AI2GreaterMAX
Check the source of the fault (parameter
32.07 Supervision 1
Check the source of the fault (parameter
32.17 Supervision 2
Check the source of the fault (parameter
32.27 Supervision 3
Check the source of the fault (parameter
32.37 Supervision 4
Fault tracing 433
37.03 ULC overload
30.17 Maximum
current.
12
AI.
signal).
signal).
signal).
signal).