Standard Ao - ABB ACS560 Firmware Manual

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

No.
Name/Value
12.110
AI dead band
0.00...100.00%
13

13 Standard AO

13.02
AO force selection
Bit
Value
0
1 = Force AO1 to value of parameter
1
1 = Force AO2 to value of parameter
2...15
Reserved
0b0000...0b1111
13.11
AO1 actual value
0.000...22.000 mA
13.12
AO1 source
Zero
Motor speed used
Output frequency
Motor current
Motor current % of
motor nominal
Motor torque
DC voltage
Output power
Freq ref used
Process PID out
Temp sensor 1
excitation
Description
Defines dead-band area for analog input signals
actual value
and
12.21 AI2 actual
For example, with dead-band as 0.40% and the default
AI1 max
as 10.000 V, the dead-band range will be 0.00... 0.04
V. In addition, considering the hysteresis value of 10%, the
hysteresis negative value will be 0.036 V and the hysteresis
positive value will be 0.044 V.
Note: 10% of the AI dead-band value is internally added to
the firmware as AI dead-band hysteresis (positive and
negative). This value cannot be changed.
For more information on dead-band function and its
calculation, see section
Deadband for AI signals.
Configuration of standard analog outputs.
The source signals of the analog outputs can be overridden
for e.g. testing purposes. A forced value parameter is
provided for each analog output, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
13.02
and 13.11).
Forced values selector for analog outputs AO1 and AO2.
Displays the value of AO1 in mA
This parameter is read-only.
Value of AO1.
Selects a signal to be connected to analog output AO1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 165).
01.08 Motor current % of motor nom
01.10 Motor torque
(page 165).
01.11 DC voltage
(page 165).
01.14 Output power
(page 166).
28.02 Frequency ref ramp output
40.01 Process PID output actual
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
source. See also section
value.
Dead-band function
on page 97.
13.13 AO1 forced
value. (0 = Normal mode)
13.23 AO2 forced
value. (0 = Normal mode)
(page 165).
(page 165).
(page 165).
(page 240).
(page 295).
35.11 Temperature 1
Motor thermal protection
Parameters 193
Def/FbEq16
12.11 AI1
0.40%
12.18
100 = 1%
0b0000
1 = 1
-
1 = 1 mA
Output
frequency
0
1
3
4
5
6
7
8
14
16
20
(page 82).