Default Control Connections For The Spfc Macro - ABB ACS560 Firmware Manual

General purpose drives
Table of Contents

Advertisement

Default control connections for the SPFC macro

1...10 kohm
Max.
500 ohm
2)
R3...R8
3)
X1
Reference voltage and analog inputs and outputs
1
SCR
2
3
AGND
4
+10V
5
6
AGND
7
AO1
8
AO2
9
AGND
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
3)
12
DCOM
13
14
15
16
17
18
X6,X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
30
31
DGND
(Frame R0...R2)
S100
TERM&BIAS
(Frame R3...R8)
S100
TERM
S200
BIAS
Safety torque off
X4
R0...R2 R3...R
33
-
34
SGND
35
OUT1 SGND
7)
36
IN1
3)
37
IN2
X10
24 V AC/DC (frames R6...R8 only)
40
24 V AC/DC- in
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0...R2)
42
+24 V
43
DGND
44
DCOM
Signal cable shield (screen)
AI1
PID setpoint, 0...10 V
Analog input circuit, common
10 V DC reference voltage
AI2
PID feedback, 4...20mA
Analog input circuit, common
Output frequency: 0...20 mA
Motor current, 0...20 mA
Analog output circuit common
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
DI1
Stop (0) / Start (1) (EXT 1)
DI2
Run enable
DI3
EXT1 (0) / EXT 2 (1)
DI4
Not configured
DI5
Not configured
DI6
Stop (0) / Start (1) (EXT 2): see
PFC1 (1st auxiliary pump)
PFC2 (2nd auxiliary pump)
B+
Internal Modbus RTU (EIA-485). See
A-
control through the embedded fieldbus interface
(EFB).
Termination resistor and bias resistor switch
Termination resistor switch
Bias resistor switch
OUT1
Safety torque off function. Factory connection.
OUT2
Both circuits must be closed for the drive to start.
See Safe torque off function in the drive
IN1
hardware manual.
IN2
24V AC/DC input, for control unit power supply
when external main power is disconnected.
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
Control macros 141
1) 5)
: see
40.16
1) 5)
: see
40.08
6)
: see
6)
: see
13.22
5)
: see
20.03
5)
: see
20.12
(if 0, drive stops).
5)
: see
19.11
20.04
6)
Running
: see
10.24
250 V AC / 30 V DC
2 A
6)
250 V AC / 30 V DC
2 A
6)
250 V AC / 30 V DC
2 A
13.12
4)
: see
10.27
: see
10.30
Fieldbus
4)