Basic control connections for E-Clipse HVAC Default

Parameter Number
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke Control mode which may
reassign the function of the other Digital Inputs. Refer to the Smoke Control (Override1) documentation.
ACH580 E-Clipse Bypass
ACH580 CONTROL BOARD
X1
1
+
2
-
3
4
5
6
7
8
9
E-CLIPSE BYPASS CONTROL BOARD
X2
1
2
3
4
5
6
7
8
9
10
X2
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25

Parameters Changed Relative to E-Clipse HVAC Default

ACH580 Installation, Operation and Maintenance Manual
Terminal for Signal Cable Shield
Analog Input 1
Analog Input Common
+10V Reference Voltage for Potentiometer
Analog Input 2
Analog Input Common
Analog Output 1
Analog Output 2
Analog Output Common
+24Vdc
+24Vdc
Digital Input Common
GND
Digital Input 1 (Parameter 1601)
Digital Input 2 (Parameter 1602,06)
Digital Input 3 (Parameter 1603)
Digital Input 4 (Parameter 1604,07)
Digital Input 5 (Parameter 1605, 1701) NOT SEL
Digital Input 6 (Fixed)
Relay Output 1 (parameter 1401) BYP NOT FLT
Default Operation: Bypass Not Faulted
Bypass Faulted
Relay Output 2 (parameter 1404) SYS RUNNING
Default Operation: System Running
Relay Output 3 (parameter 1407) SYS STARTED
Default Operation: System started
Relay Output 4 (parameter 1410) BYPASS SEL
Default Operation: Bypass selected
Relay Output 5 (parameter 1413) BYPASS AUTO
Default Operation: Bypass auto
Description
START/STOP
NOT SEL
START INTERLOCK 1
NOT SEL
SMOKE CONTROL*
(OVERRIDE 1)
11 connected to 13
11 connected to 12
14 connected to 16
17 connected to 19
20 connected to 22
23 connected to 25
Setting