Built-in Positioning Functions
CLEAR signal device specification method:
1) Write the CLEAR signal output (Y) device number in the "CLEAR signal device specification" register with
a hexadecimal number (expressed in octal numbers).
e.g. setting H0010 means Y010. When setting H0008, an operation error occurs because Y008 does not
exist.
2) Turn on the "CLEAR signal output function enable" relay and "CLEAR signal device specification function
enable" relay to specify the CLEAR signal device.
3) Execute the DSZR instruction (zero return instruction with DOG search function) or ZRN instruction (zero
return instruction).
Example program:
The following figure shows a program that can specify Y010 as the CLEAR signal output device for Y000
(pulse output destination device):
M8000
RUN
monitor
4.3.5

Change in Logic of Near-Point (DOG) Signal (DSZR Instruction)

Turn on or off the "DOG signal logic reverse" relay to specify the logic of the near-point (DOG) signal of the
DSZR instruction (zero return instruction with DOG search function). Use the operand (
instruction to specify the near-point (DOG) signal.
Pulse output
destination device
Y000
Y001
*1
Y002
*2
Y003
*1.
Y002 is not available in FX
*2.
Y003 is available only when two high-speed output special adapters are connected to the FX
4.3.6

Change in Logic of Zero-Phase Signal (DSZR Instruction)

Turn on or off the Zero-point signal logic reverse" relay to specify the logic of the zero-phase signal of the
DSZR instruction (zero return instruction with dog search function). Use the operand (
to specify the zero-phase signal.
Pulse output
destination device
Y000
Y001
*1
Y002
*2
Y003
*1.
Y002 is not available in FX
*2.
Y003 is available only when two high-speed output special adapters are connected to the FX
PLC User's Manual - Positioning Control Edition
FNC 12
H0010
D8464
MOVP
M8464
M8341
"DOG signal logic
reverse" relay
M8345
M8355
M8365
M8375
PLC (14-point and 24-point type) and FX
3G
"Zero-point signal
logic reverse" relay
M8346
M8356
M8366
M8376
PLC (14-point and 24-point type) and FX
3G
4.3 Various Special Relays for Operation Commands
Specifies the Y010 as the CLEAR signal output device for
Y000 (pulse output destination device).
Turns on "CLEAR signal device specification function enable"
relay for Y000 (pulse output destination device).
Turns on the "CLEAR signal output function enable" relay.
For operation of DSZR instruction, refer to Section 6.2.
Description of setting
OFF:
Positive logic (Turning on the input will turn on the near-
point signal.)
ON:
Negative logic (Turning off the input will turn on the near-
point signal.)
For operation of DSZR instruction, refer to Section 6.2.
Description of setting
OFF:
Positive logic (Turning on the input will turn on the zero-
phase signal.)
ON:
Negative logic (Turning off the input will turn on the zero-
phase signal.)
4 Before Programming
) of the
S
1
/FX
PLC.
3S
3GC
PLC.
3U
) of the instruction
S
2
/FX
PLC.
3S
3GC
PLC.
3U
B - 61
A
B
Apx.