Example Connection
2. FX
/FX
PLC
3G
3U
FX
-40MT/ES
3G
FX
-32MT/ES
3U
Photo-coupler
*3
FX
-16EYT
2N
FX
-16EX-ES/UL
2N
Photo-coupler
Be sure to use the class-D grounding method (grounding resistance: 100  or less).
*1.
*2.
For details on the MR-J2(S) servo amplifier, such as the tolerance for the internal power and operation of the servo
amplifier, refer to the following manual.
*3.
Extension blocks are used in the connection example.
Inputs and outputs built into the main unit are available in place of extension blocks.
PLC User's Manual - Positioning Control Edition
100 to 240 V AC
L
N
Class-D
grounding
*1
S/S
0V
24V
X000
COM1
Y020
Servo-ON
Y021
ABS transfer mode
Y022
ABS request
Y023
Y027
*3
S/S
X020
ABS (bit0)
X031
ABS (bit1)
X032
Send data ready
X033
X037
Appendix 4. MELSERVO-J2 (-Super) Series
Appendix 4-3 Absolute Position Detection (Transistor Output)
MR-J2(S)A
Series servo
amplifier
CN1B
SG
10
COM
13
VDD
3
*2
SON
5
ABSM
8
ABSR
9
DO1
4
ZSP
19
TLC
6
SD
Plate
For details, refer to the servo amplifier manual.
A
B
Apx.
Apx. - 39