Mitsubishi Electric Melsec-F FX3GC Series User Manual page 263

Hide thumbs Also See for Melsec-F FX3GC Series:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Example Connection
2. FX
/FX
PLC
3G
3U
100 to
240 V AC
FX
-40MT/ES
3G
L
FX
-32MT/ES
3U
N
Class-D
grounding
S/S
0V
24V
X000
Photo-coupler
X004
X010
DOG
X014
X017
*7
COM1
Y000
*8
COM2
Y004
Y007
*6
FX
-16EYT
2N
COM1
Y020
Y027
*6
FX
-16EX-ES/UL
2N
S/S
X020
X021
Photo-coupler
X022
X023
X024
X025
X026
X027
X030
X037
Be sure to use the class-D grounding method (grounding resistance: 100  or less).
*1.
*2.
Near-point signal (DOG)
PLC User's Manual - Positioning Control Edition
*1
Zero-Point
signal (PG0)
Servo ready
(RD)
*2
Pulse train
Direction
CLEAR signal
Immediate stop
command
Zero return command
Positioning
JOG (+) command
completed (INP)
JOG (-) command
Forward rotation positioning command
Reverse rotation positioning command
Forward rotation limit 1 (LSF)
Reverse rotation limit 1 (LSR)
Stop command
Appendix 4. MELSERVO-J2 (-Super) Series
Appendix 4-1 Main Unit (Transistor Output)
MR-J2(S)A
CN1B
Series servo
amplifier
10
SG
*4
3
VDD
13
COM
6
TLC
18
ALM
19
ZSP
CN1A
CN1B
LG
1
5
SON
OP
14
RES
14
15
EMG
RD
19
16
LSP
17
LSN
20
SG
SG
10
PP
3
CN1B
4
DO1
NP
2
19
ZSP
6
TLC
10
SG
5
SON
8
ABSM
9
ABSR
CR
8
SD
Plate
CN1A
COM
9
OPC
11
INP
18
*3
*3
Torque being controlled
*5
Servo error (ALM)
Zero speed
*5
Servo-ON
*5
Reset
Emergency stop
Forward rotation limit 2
*3
Reverse rotation limit 2
*3
*5
Connected to the
PLC if the ABS
instruction (FNC155)
is used.
FX
-16EX-ES/UL
2N
FX
-16EYT
2N
Refer to Appendix
4.3.1-2.
Apx. - 33
A
B
Apx.

Advertisement

Table of Contents
loading

Table of Contents