Built-in Positioning Functions
2. Zero return instruction (ZRN instruction)
Zero return will be performed in the reverse rotation direction only.
(During zero return, the value indicated by the current value register will be decreased.)
To perform zero return in the forward rotation direction using the ZRN instruction (zero return instruction):
To perform zero return in the forward rotation direction, create a program to control the output (Y) relay set as
a "rotational direction signal" as follows:
a) Turn on Y (rotational direction signal).
b) Refresh Y output using the REF (FNC 50) instruction.
c) Execute the ZRN instruction (zero return instruction).
d) Using the execution completion flag (M8029) of the ZRN instruction (zero return instruction), reset Y
(rotational direction signal).
Example program:
The following program uses Y004 as the rotational direction signal for Y000.
Command
input
M12
PLC User's Manual - Positioning Control Edition
To use
To use a high-speed output special adapter, refer to Section 4.9.
FNC 50
REFP
FNC156
S
1
DZRN
M8029
M8329
4.3 Various Special Relays for Operation Commands
For details on programming, refer to Section 4.7.
main unit (transistor output), refer to Section 4.8.
the
RST
M10
RST
M11
SET
M12
a)
SET
Y004
b)
Y000
K8
c)
S
S
Y000
2
3
d)
RST
Y004
SET
M10
Origin data reading completion flag
RST
M12
Resets the rotational direction signal
RST
Y004
(Y004) using the instruction
execution abnormal end flag.
SET
M11
Abnormal end of zero return
RST
M12
4 Before Programming
Turns on (sets) Y004 as the
rotational direction signal of Y000
(pulse output destination).
Refreshes Y000 to Y007.
Executes ZRN instruction.
Resets the rotational direction
signal (Y004) using the instruction
execution complete flag.
B - 59