Caution For Using The High-Speed Output Special Adapter - Mitsubishi Electric Melsec-F FX3GC Series User Manual

Hide thumbs Also See for Melsec-F FX3GC Series:
Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Built-in Positioning Functions
4.9

Caution for Using the High-Speed Output Special Adapter

(FX
-2HSY-ADP)
3U
1. Output terminals to be used
If the high-speed output special adapter is connected, output numbers will be assigned in the same way as
the main unit as shown in the following table. Use the output terminals of one side (main unit side or high-
speed output special adapter side), and do not connect lines to the output terminals of the unused side.
The outputs of the high-speed output special adapter and the main will operate as follows.
Assignment of output numbers
Position of pulse output method
setting switch of high-speed
output special adapter
FP
RP side
PLS
Operation of output
Unit
FX
Series main unit
3U
of relay output type
FX
Series main unit
3U
of transistor output
type
FX
Series main unit
3U
of triac output type
High-speed output
special adapter
*1.
The output frequency limit of the main unit transistor output is 100 kHz. When operating a load with a
pulse frequency exceeding 100 kHz, PLC failure may occur.
*2.
Furthermore, use of the PWM (FNC 58) is not recommended with the relay type main unit and the
high-speed adapters due to chattering of the relay contacts.
*3.
The PWM instruction does not support the triac output due to response delay of outputs.
• If an output number of the high-speed output special adapter is used (if an output of the high-speed output
special adapter is connected), do not use (connect) the corresponding output terminal of the main unit.
• If an output number of the main unit is used (if an output of the main unit is connected), do not use
(connect) the corresponding output terminal of the high-speed output special adapter.
B - 86
PLC User's Manual - Positioning Control Edition
Forward rotation
pulse train (FP)
Reverse rotation
pulse train (RP)
Pulse train
DIR side
Direction
PLSY,PLSR,DSZR,
DVIT,TBL,ZRN,PLSV,
DRVI,DRVA instruction.
While instruction is
activated, relevant
output is ON. (LED is
also ON.)
*1
Operated
While instruction is
activated, relevant
output is ON. (LED is
also ON.)
Operated
4.9 Caution for Using the High-Speed Output Special Adapter (FX3U-2HSY-ADP)
Name of
Signal
positioning
instruction
Pulse output
destination
Rotation
direction signal
Pulse output
destination
Rotation
direction signal
Output operation
PWM instruction
Use of the PWM (FNC 58) instruction is not
compatible with a relay type main unit.
Operated
Use of the PWM (FNC 58) instruction is not
compatible with a triac type main unit.
Operated
The main unit should use the transistor output
*2
type.
4 Before Programming
Output number
1st adapter
2nd adapter
1st axis 2nd axis 3rd axis 4th axis
Y000
Y001
Y002
Y004
Y005
Y006
Y000
Y001
Y002
Y004
Y005
Y006
*2
*3
Y003
Y007
Y003
Y007
Other
instruction
Operated
Operated
Operated
Operated