Important information on: Operating modes and functions
If the temperature reaches 25 °C, the sun protection function is
reached and the shutters close to 50 %. If the brightness value
undershoots 50 %, the shutters move to the starting position
(OPEN) again.
If the outside temperature drops below 20 °C, sun protection is
deactivated, regardless of the brightness value. The shutters
then remain in their current position.
For information on adapting the setpoint for the functions de-
scribed above, please read the Chapter entitled "Setting tem-
perature-dependent sun protection (shading) of a shutter" from
Page 78 onwards.
If outside and inside temperature sensors are installed for this
function, sun protection is deactivated if the inside and outside
temperatures are below the threshold values. Sun protection is
activated as soon as one of the 2 temperatures exceeds the
corresponding threshold value.
Remote access to radiator controller HR 50
To control the radiator controller HR 50 via a setpoint adjuster
HCW 22 or a temperature sensor HCF 22, the devices must be
assigned to the same room at the Hometronic Manager
HCM 200d.
The HCM 200d displays the room temperature of the HCW 22
here. The temperature offset is displayed by an arrow in the
menu:
Arrow up
Arrow down = minus
No arrow
If a temperature sensor HCF 22 is installed, only the room tem-
perature without the offset is sent to the Hometronic Manager.
For information on setting the radiator controller HR 50, please
read the Chapter entitled "Activating Manual mode " from Page
33 onwards.
= plus
= offset 0